Problem Symptoms And Measures - Daikin FTXN09KEVJU Service Manual

Inverter pair wall mounted type k-series
Hide thumbs Also See for FTXN09KEVJU:
Table of Contents

Advertisement

Problem Symptoms and Measures

2. Problem Symptoms and Measures

Symptom
The unit does not operate. Check the power supply.
Operation sometimes
stops.
The unit operates but does
not cool, or does not heat.
Large operating noise and
vibrations
74
Check Item
Check the type of the indoor unit.
Check the outdoor temperature.
Diagnose with remote controller
indication.
Check the remote controller
addresses.
Check the power supply.
Check the outdoor temperature.
Diagnose with remote controller
indication.
Check for wiring and piping errors in
the connection between the indoor
unit and outdoor unit.
Check for thermistor detection errors. Check if the thermistor is mounted securely.
Check for faulty operation of the
electronic expansion valve.
Diagnose with remote controller
indication.
Diagnose by service port pressure
and operating current.
Check the output voltage of the
power module.
Check the power module.
Check the installation condition.
Details of Measure
Check if the rated voltage is supplied.
Check if the indoor unit type is compatible with the
outdoor unit.
Heating operation cannot be used when the
outdoor temperature is 24°C (75.2°F) or higher,
and cooling operation cannot be used when the
outdoor temperature is below 10°C (50°F).
Check if address settings for the remote controller
and indoor unit are correct.
A power failure of 2 to 10 cycles stops air
conditioner operation. (Operation lamp OFF)
Heating operation cannot be used when the
outdoor temperature is 24°C (75.2°F) or higher,
and cooling operation cannot be used when the
outdoor temperature is below 10°C (50°F).
Set the unit to cooling operation, and check the
temperature of the liquid pipe to see if the electronic
expansion valve works.
Check for refrigerant shortage.
Check if the required spaces for installation
(specified in the installation manual) are provided.
SiUS041111
Reference
Page
78
225
78
78
112
126
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents