HP BladeSystem c7000 Setup And Installation Manual page 30

Bladesystem c7000 carrier-grade enclosure
Hide thumbs Also See for BladeSystem c7000:
Table of Contents

Advertisement

To join two cabinets together, you need two brackets, 12 round washers, and four 5/8-inch bolts.
Cabinets are joined at the top at two anchor positions. For each anchor position:
1.
For the seismic rack: For information on how to orient the bracket when connecting a seismic
rack to other seismic racks, see
For the seismic rack R2: For information on how to orient the bracket when connecting a
seismic rack to other seismic racks, see
2.
Stack two washers on top of the anchor holes in the two adjacent cabinets.
3.
Stack the brackets on top of the washers.
4.
Stack one washer on top of each hole in the bracket.
5.
Insert a 5/8-inch bolt in each of the holes. See
and bracket components.
6.
Using a hex driver, tighten the bolts to 59 in-lbs (6.7 N-m).
From left to right,
Figure 3 Joining a Seismic Rack to other Seismic Racks (top view)
From left to right,
is connected to another seismic rack R2.
Figure 4 Joining a seismic rack R2 to other Seismic Racks (top view)
30
Installation
Figure 3 (page
Figure 3 (page 30)
shows three seismic racks connected to each other.
Figure 4 (page 30)
shows a seismic rack connected to a seismic rack R2, which
30).
Figure 4 (page
30).
Figure 5 (page 31)
for the stack-up of the bolt