Generator Outputs - MULTIQUIP Whisperwatt dca25ssiu3 Operation And Parts Manual

Whisperwatt series 60hz generator
Hide thumbs Also See for Whisperwatt dca25ssiu3:
Table of Contents

Advertisement

how To reaD The aC aMMeTer anD aC
voLTage gaUgeS
The AC ammeter and AC voltmeter gauges are controlled
by the AC ammeter and AC voltmeter change-over
switches.
Both of these switches are located on the control panel and
Do noT effect the generator output. They are provided to
help observe how much power is being supplied, produced
at the UVWO terminals lugs.
Before taking a reading from either gauge, set the Voltage
Selector Switch (Figure 14) to the position which produces
the required voltage (For example, for 3Ø 240V, choose
the center 3Ø 240/139V position on the voltage selector
switch).
Figure 14. Voltage Selector Switch
240/139V 3
NOTICE
For 3Ø 208V/1Ø,120V, place the Voltage Selector
Switch in the 3 Phase 240/139 position.
aC voltmeter gauge reading
Place the AC Voltmeter Change-Over Switch (Figure 15)
in the W-U position and observe the phase to phase voltage
reading between the W and U terminals as indicated on
the AC Voltmeter Gauge (Figure 16)
Figure 15. aC voltmeter
Change-over Switch
DCa25SSIU3 (wITh MLT25 SerIeS) • operaTIon anD parTS ManUaL — rev. #1 (01/24/13) — page 25
generatOr Outputs/gauge reading
Ø Position
Figure 16. aC voltmeter
gauge
aC ammeter gauge reading
Place the AC Ammeter Change-Over Switch (Figure 17)
in the U position and observe the current reading (load
drain) on the U terminal as indicated on the AC Ammeter
Gauge (Figure 18). This process can be repeated for
terminals V and W.
Figure 17. aC ammeter
Change-over Switch
NOTICE
The ammeter gauge will only show a reading when
the Output Terminal Lugs are connected to a load
and in use.
Figure 18. aC ammeter
(amp reading on U Lug)