7400 Series UPS User Manual
Single Module and One plus One Systems
OUTPUT RATINGS
Voltage
Frequency
Power at 0,8pf
Power at 1,0pf
Overload ability at 0,8pf
3
1
Current limiting short circuit (inverter)
150% rated current (3 phase) for
220% rated current (1 phase) for
Maximum permissible non linear load
Voltage stability
steady state
Voltage stability
transient state
Reset time to within 1%
Frequency stability
synchronised
Frequency stability
unsynchronised
Phase voltage asymmetry
balanced load
Phase voltage dissymmetry
100%
unbalanced load
Voltage phase shift
with balanced load
6310018a.02.doc
UNITS
80
6 Pulse
12 Pulse
6 Pulse
V a.c.
Hz
kVA
80
kW
64
%
The output will synchronise with the input supply within 1 Hz of nominal frequency (adjustable to 2 Hz)
Angle°
Model kVA Rating
120
200
12 Pulse
6 Pulse
12 Pulse
380/400/415 (preset on commissioning) 3 Ph N
50 or 60 (presettable)
120
200
96
160
110% for 60 minutes
125% for 10 minutes
150% for 1 minute
200% for 30 seconds
< 5 seconds
< 5 seconds
100 with 3:1 crest factor
1%
5%
20 ms
0,1% when the input supply frequency is outside the synchronising range
1%
2 %
120
1
Chapter 7 - Specificatio
300
400
6 Pulse
12 Pulse
6 Pulse
300
400
240
320
12 Pulse
7-
Issue
(02/9