Safety Precautions - Liebert 7400 Series User Manual

Single module and 1+1 configuration
Table of Contents

Advertisement

7400 Series UPS
Single and 1+1 IOM Manual
THIS UPS DOES NOT INCORPORATE AUTOMATIC BACKFEED PROTECTION. A
WARNING LABEL MUST BE FITTED TO ALL EXTERNAL PRIMARY POWER
ISOLATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THIS
In common with other types of high power equipment, dangerous voltages are present within the UPS
and battery enclosure. The risk of contact with these voltages is minimised as the live component parts
are housed behind a hinged, lockable door. Further internal safety screens make the equipment
protected to IP20 standards. No risk exists to any personnel when operating the equipment in the
All equipment maintenance and servicing procedures involve internal access and should be carried out
Battery manufacturers supply details of the necessary precautions to be observed when
working on, or in the vicinity of, a large bank of battery cells. These precautions should be
Particular attention should be paid to the recommendations concerning local environmental
conditions and the provision of protective clothing, first aid and fire-fighting facilities.
When the battery is under charge it is earth-referenced about its mid-point e.g. if the battery
is being charged at 446 V the battery extremities will be at +223V and -223V with respect to
neutral (earth). When using mains-powered test equipment such as oscilloscopes in the UPS
high voltage area, always use a differential mode of operation to avoid the need to
When working inside the UPS (trained personnel only) it is recommended that protection be
worn to prevent eye damage, should an electrical arc be struck by mishandling or severe
Some of the power components are very heavy. If their removal is necessary ensure that
sufficient manpower is available, otherwise use adequate mechanical handling
equipment.When working in the general area of the UPS where high voltages are present, a
second person should be standing-by to assist and summon help in case of accident.

Safety Precautions

WARNING
ISOLATORS STATING:
normal manner, following the recommended operating procedures.
only by trained personnel.
followed implicitly at all times.
Test Equipment
disconnect the oscilloscope frame earth.
electrical fault.
6310018a.02.doc
CIRCUIT.
General
Batteries
Personnel
Prelim v