Use Up/Down buttons to move the cursor to the Main Fan, and press Enter to enter
the Main Fan Service Interval sub-menu, as shown in Figure 5-16.
The Run Time is the actual operation days of the component. It is real time clock
counter days and is unchangeable.
The Chng Time is the recommended operation days of the component. It can be
changed. The default value is recommended. Otherwise change it according to the
actual condition.
The Reset indicates whether the component has been maintained or replaced or
not. Select YES if it is maintained or replaced, and the service time will be reset to
zero automatically and then be recounted again. Otherwise, select NO.

5.7 Setpoints

The setpoints will not be lost when power fails. Select the Setpoints from the main
menu and press Enter to configure the setpoints listed in Figure 5-17.
Use the Up/Down buttons to select a certain item and press Enter to access the
input data field. Use the Up/Down buttons again to increase or decrease the digit.
Press Enter to validate the new setpoint.
Refer to Table 5-1 for the defaults of the setpoints in Figure 5-17 and their setting
ranges.
M
a i n
H u m i d i f i e r
F i l t e r
Figure 5-15 Service Interval menu
R
u n
C h n g
R e s e t
Figure 5-16 Main Fan Service Interval sub-menu
T
e m p S t p t
T e m p B i a s
H u m S t p t
H u m B i a s
Figure 5-17 Setpoints menu
DataMate 3000 Series Air Conditioner User Manual
Chapter 5 Microprocessor Control
F a n
T i m e
1 0 0 d
T i m e
3 6 0 d
N O
2 4
3
5 0 % R H
5 % R H
39