1. Present an editor key to the faceplate reader.
2. Enter the password and press [ENT], if required.
3. You will now see the CMD prompt.
4. Type [M][R] and press [ENT].
CMD MR_
5. Use the up and down arrow keys to select a
response. There are a maximum of 255
responses.
Manual Switch
REC 1
ON
Type [Y] to switch on the response. Press [ENT].
Type [N] to switch off the response. Press [ENT].
Note:
Any points that have been assigned this response will be
disabled if you select [N], or enabled if you select [Y].
Press [NXT] to go to the next field.
6. Time Profile - Enter the time profile number
used to control the response. When the time
profile is active, any points assigned this response
will be disabled.
REC 1
TP
A time profile of 0 means any points assigned
this response will be controlled only by the
manual switch. Press [ENT].
Press [ESC] to return to the CMD prompt..
Alarm Module Sensors
The MS Command: Each alarm module input is
enabled by giving it a response number using the
MR command (see Alarm Module Responses – The MR
Command) In addition, each input may be
programmed to operate a relay on any alarm module
on the same door controller.
Response Number
By giving one or more inputs the same response
number, several points can be controlled together.
The number you enter is the record number of the
response you create using the MR command.
Alarm Module Relay
Any alarm module relay on the same door controller
can be set when a point is activated. The number you
enter is the number of the relay according to the
table.
Bosch Security Systems | 7/03 | 17376 v1.1 / 47491C
Installer Commands
N
0
Table 23: Relay Numbers
Module Location
Channel 1
Channel 2
Channel 3*
Channel 4*
13
* Not available on Readykey K1200 door
controllers
Note:
The fourth relay on alarm module 4 is not available for
alarm input activation
Using the MS Command
Use the MS command to assign responses to alarm
module inputs. Each record contains responses for all
8 inputs on each alarm module.
1. Present an editor key to the faceplate reader.
2. Enter the password and press [ENT], if required.
3. You will now see the CMD prompt.
4. Type [M][S] and press [ENT].
CMD MS_
5. Use the up and down arrow keys to select an
alarm module. There are a maximum of 16
alarm modules.
6. Input 1 Response Number - Enter the response
number for this input. If you enter [0], the input
will not be monitored at all. Press [ENT].
DR 1
IP 1 R 0
Press [NXT] to go to the next field.
7. Input 1 Module Relay - Enter a relay number,
see the table above, that will be set if the input is
activated. Enter [0] for no relay activation. Press
[ENT].
MODULE RELAY
0
Press [NXT] to go to the next field.
8. Input 2 Response Number - Enter the response
number for this input. If you enter [0], the input
will not be monitored at all. Press [ENT].
DR 1
IP 2 R 0
Press [NXT] to go to the next field.
9. Input 2 Module Relay - Enter a relay number,
see the table above, that will be set if the input is
activated. Enter [0] for no relay activation. Press
[ENT].
MODULE RELAY
0
Press [NXT] to go to the next field.
Press [ESC] when you have finished.
EN | 48
Relays
1
2
3
4
5
6
7
8
9
10
11
12
14
15
n/a