Bosch K2200 Series User Manual page 43

Readykey controllers
Table of Contents

Advertisement

K2200 Series | User Guide | 6.0
If a value of 0 is used, a key will be required at
all times.
If a time profile is disabled, the door it is
assigned to will lock (if it is unlocked) and a key
Mode 1
Prompt:
Range:
Default:
Table 17: Reader and Lock Operation Settings – Mode 1
Option
Type
1
Lock Type
2
Emergency
Override/Free Exit
3
Request for Entry
4
Readykey AVR
(Automatic Vehicle
Recognition)
5
Readykey Alarm
Module/Readykey
Alarm Event Manager
6
Exit Out of Hours
Bosch Security Systems | 7/03 | 17376 v1.1 / 47491C
Installer Commands
M
8 options
All unset
Description
Power to unlock, fail-secure
Unset:
Power to lock, fail-safe
If you using a power to lock (or fail-safe) locking device, this option should be set. In
this case, power will be provided continuously and removed to release the lock. If
unset, power will be provided to operate the lock
Unset:
Normal Operation
Set:
Emergency Override/Free Exit
The operation of this option is described in detail in the Readykey K2200 Series
Controllers Installation Guide (Bosch P/N: 46513, PAC P/N: 17375).
When unset the DR1 inputs operate normally:
DR1
the door contact switch, if fitted, monitors the door position
DR2
the Request to Exit switch
When this option is set, the operation of the DR1 and DR2 inputs is altered:
DR1
the door contact switch, produces a Free Exit transaction. It may also
operate as a Request to Exit switch, in that if it is opened the lock will
also operate. A door open time must be set to allow this feature to
operate. Door left open reports will also be generated if it is used as
a door monitoring switch.
when opened produces an Emergency Override On transaction,
DR2
when closed produces an Emergency Override Off
transaction. This allows the monitoring of an emergency switch such
as a break-glass.
Unset:
Normal Operation
Set:
Request for Entry
When set, a Request to Exit switch will produce a Request for Entry transaction. This
is a useful feature, for instance, when the switch is operated from inside an area to
unlock a door once a person outside has been recognized. This may the case when
using audio or video entry systems.
No AVR attached
Unset:
AVR
Set:
Only set this option when a Readykey AVR reader module is attached to the reader
channel.
Unset:
No Readykey Alarm Module/Readykey Alarm Event Manager
attached.
Readykey Alarm Module/Readykey Alarm Event Manager
Set:
Only set this option when an alarm module is fitted to the reader channel. If you set
this option when an alarm module is not attached the reader LED will flicker. You
cannot have both option 7 (PIN reader with time profiles) and a Readykey Alarm
Module set on the same channel.
Unset
Normal Operation
Exit Out Of Hours
Set
will be required at all times until the time profile
is enabled again.
This option field controls 8 different settings
controlling the operation of the reader and lock.
They are:
EN | 43