NetPro 19" model
Ratings
Voltage Amperes (VA)
with computer type load
Watts (W)
with resistive load
Input thermal circuit breaker (A)
Input fuse (A)
Input converter
AC input voltage
AC input voltage range
Minimum start-up AC voltage
Input current waveform
Input current (A) at nom. inp. volt.
Input power factor
Input frequency range
Inrush current
Output converter
AC output voltage
AC output voltage tolerance
Output frequency
Output frequency range
Output waveform
Harmonic distortion
Power factor
Crest factor (peak to RMS current)
Capacity appliance outlets
Bypass
AC input voltage range
Frequency tracking rate
Frequency tracking range
Phase difference
Typical transfer time, msec
Overload capability
Overload behaviour (battery operation)
Overload behaviour during
bypass operation
Batteries (ratings given for 25ºC)
Nominal voltage (Vdc)
Number of 7 Ah batteries
Type
Service life
Recharge current
Battery recharge time
(batt. discharged at 100% load)
Runtime in minutes
at typical load (75%)
VA/Watts
100/60
200/120
400/240
600/360
1000/600
1500/900
General
Weight without battery drawer (kg)
Weight with battery drawer (kg)
Dimensions (hxwxd, mm)
Depth required in 19" rack (mm)
Enclosure / protection
Environment
Safety
Electromagnetic compatibility
Ambient temperature
Audible noise at 1 meter
Max. relative humidity
OPM_NPE_19X_600_1K5_2GB_V030

8 - Specifications

:
600
1000
:
600
1000
:
360
600
:
5
5
:
8
8
:
220 - 240 V
:
100% load: 187 - 264 V
70% load: 120 - 264 V
input >264 Vac: UPS switches to battery operation
input >312 Vac: UPS shuts down, manual restart required
:
187 V (at any load)
:
sinusoidal
conform or better than EN 61000-3-2 (IEC 555-2)
:
2.0
3.3
:
1
:
45 - 66 Hz
:
none
:
230 V (suitable for 220 - 240 V loads)
:
± 2%
:
50 or 60 Hz, front selectable
:
nominal ± 0.15% unless synchronized to the mains
:
sine wave
:
< 2% (typical 1.5%) with linear load
:
0.6 (0.7 at 90% load)
:
suitable for loads with c.f. up to 6:1
:
max. 10 A per outlet
:
195 - 264 V
:
2 Hz/sec.
:
nominal ± 10%
:
< 7º
:
4
:
Fully protected against overload and short circuits
:
110% during 5 minutes; 150% during 5 seconds
:
depends on rating of thermal circuit breaker
typical:
125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds
:
24
36
:
2
3
:
sealed lead acid, maintenance free
:
up to 6 years (depending on use)
:
1.5 A
:
1.5 hours for 90% capacity, std battery
:
12
12
:
64
104
:
34
54
:
15
27
:
9
15
:
-
9
:
-
-
:
14
14
:
19
22
:
133.5 (3HU) x 450 (19") x 440
:
420 (without connectors)
:
steel - plastic / IP20
:
EN 50091-1-1, EN 60950, IEC 950
:
EN 50091-2
:
-10 to +40ºC
:
< 45 dB(A), load and temperature dependent
:
95% (non-condensing)
13
GE DE NetPro 19" 600-1500: User manual 3.0 (GB)
GE Digital Energy
1500
1500
900
7
10
5.0
48
4
10
124
71
36
24
12
6
14
24

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Digital energy netpro 19”

Table of Contents