Windows

Do not house computers in a room with windows. Sunlight entering a computer room can cause
problems. Magnetic tape storage media is damaged if exposed to direct sunlight. Also, the heat
generated by sunlight places an additional load on the cooling system.

Space Requirements

This section contains information about space requirements for the product. Use this data as the
basic guideline for space plan developments. Also consider factors such as airflow, lighting, and
equipment space requirements.

Delivery Space Requirements

The site must have enough clearance to move equipment safely from the receiving area to the
computer room. Permanent obstructions such as pillars or narrow doorway's can cause equipment
damage.
Include the possible removal of walls or doors in the delivery plans.

Operational Space Requirements

Consider the following factors in addition to the basic equipment dimensions:
Eliminate obstructions to equipment intake or exhaust flow.
Determine locations of lighting fixtures and utility outlets affecting servicing operations.
Plan equipment layout to take advantage of lighting and utility outlets. Do not forget to
include clearance for opening and closing equipment doors.
Provide sufficient clearance around the cabinets for proper cooling airflow through the
equipment.
If other equipment is located so that it exhausts heated air near the cooling air intakes of the
product cabinets, more space is needed to keep ambient air intake to the product cabinets within
the specified temperature and humidity ranges. See
Installations
for operating ranges. Additional information is available from the following section:
Air Quality (page
Table 1-5 Typical Environments of Customer Installations
Environment
Running at extremes
should consider
upgrading the facility.
Controlled Computer
4
Room
Office
Home
Light Industrial
(including closets)
Portable/Mobile
Special (or Contract)
16).
Operating Environment (ambient)
2
Temp ºC, dry bulb
(ºF)
18 to 27
(65 to 81)
5 to 35
(41 to 95)
5 to 35
(41 to 95)
5 to 40
(41 to 104)
5 to 40
(41 to 104)
Product specifications controlled by contract or other requirements.
Table 1-5: Typical Environments of Customer
1
Relative Humidity %:
Dew-point
Noncondensing
(max)
20 to 80
17
8 to 85
28
8 to 85
28
8 to 90
28
8 to 90
28
Rate of Chg ºC/hr,
3
max
(ºF/hr, max)
5
(41)
5
NA
5
NA
5
NA
5
NA
Space Requirements