Dust and Pollution Control

Computer equipment can be adversely affected by dust and microscopic particles in the site
environment.
Specifically, disk drives, tape drives, and some other mechanical devices can have bearing failures
resulting from airborne abrasive particles. Dust might also blanket electronic components such
as printed circuit boards, causing premature failure due to excess heat or humidity buildup on
the boards. Failures to power supplies and other electronic components can be caused by
metallically conductive particles, including zinc and tin whiskers. These metallic particles are
conductive and can short circuit electronic components. Use every effort to ensure that the
environment is as dust- and particulate-free as possible. See
(page 21)
for additional details.
Smaller particles can pass through some filters and cause short life cycles in mechanical parts.
Prevent small dust particles from entering the computer room by maintaining the air-conditioning
system at a high static air pressure level.
Other sources of dust, metallic, conductive, abrasive, and microscopic particles can be present.
Some sources of these particulates are:
Subfloor shedding
Raised-floor shedding
Ceiling-tile shedding
These particulates are not always visible to the naked eye. One method to determine their possible
presence is to inspect the underside of the tiles. For more information, see
Contamination" (page
There are two types of flooring:
a.
galvanized – shiny – hot dipped: least susceptible for whiskers
b.
painted – dull – electroplating: most susceptible for whiskers
Another Best Practice to control dust and particulates is with the use of sticky mats (adhesive
coated mats) at doorway entrances to the computer room. In the majority of environments, there
is more particulate matter on the feet than anywhere else, including air exchange. Popular brands
have multiple layers that allow the top layer to be peeled off for disposal prior to losing all
adhesive properties. This provides the next fresh sheet to be exposed to continue effective capture
of particulate matter.
Keep the computer room clean by following these guidelines:
Establish a no-smoking policy. Particulates of cigarette smoke will not improve the operation
or reliability of surrounding equipment.
Locate printers and paper products in a separate room to eliminate paper particulate
problems.
Establish a no-eating-or-drinking policy. Spilled liquids can cause short circuits in equipment
such as keyboards.
Use a dust-absorbent cloth mop rather than a dry mop to clean tile floors.
Use only HP-approved cleaners.
IMPORTANT:
must not exceed G1 (mild) levels of Group A chemicals at any time. For more information, see
Table 1-1 (page
In addition to dust and microscopic particles, chemical contaminants in the air can also damage
electronics. Chemical contaminant levels in customer environments for HP hardware products
must not exceed G1 (mild) levels of Group A chemicals at any time, as described in the current
version of ISA–71.04 Environmental Conditions for Process Measurement and Control Systems: Airborne
Contaminants.
20
General Site Preparation Guidelines
21).
Air quality must meet the following quality standards. Gaseous contamination
21).
"Metallic Particulate Contamination"
"Metallic Particulate