UPS Alarm List
ID
Object
1
.../upsAlarmBat
teryBad
2
.../upsAlarmOn
Battery
3
.../upsAlarmLo
wBattery
4
.../upsAlarmDe
pletedBattery
5
.../upsAlarmTe
mpBad
6
.../upsAlarmInp
utBad
7
.../upsAlarmOu
tputBad
8
.../upsAlarmOu
tputOverload
9
.../upsAlarmOn
Bypass
10
.../upsAlarmBy
passBad
Alarm Occur Message
Battery test has detected
battery failure. Contact
Toshiba authorized service
center for replacement.
The UPS is on batteries; it is
supplying output power from
its batteries.
Low battery. Continued
operation on batteries will
deplete them entirely & result
in UPS Output shutdown.
UPS has depleted batteries &
unable to support critical
loads. Turn off excess
equipment to reduce load.
The UPS is overheating.
Check for UPS fan failure or
high ambient temperature ( >
40°C / 104°F)
The input voltage is out of
tolerance. UPS may switch to
Battery Mode to support the
load.
The output voltage is out of
tolerance. Check the output
voltage.
UPS is overloaded. UPS will
switch to bypass or shutdown.
Turn off excess equipment to
reduce load.
The UPS is in Stop (Bypass)
mode.
A bypass condition is out of
tolerance. Check the input
and output voltage.
Alarm Removal Message
Battery failure condition, detected
by previous battery test, has been
removed.
The UPS is no longer on batteries;
output power is not being supplied
from its batteries.
The UPS is no longer reporting a
state of Low Batteries.
The batteries are no longer
depleted; they have been charged to
a supportive level.
The UPS is no longer overheating.
The input voltage is back within
tolerance.
N/A
The UPS is no longer being
overloaded.
The UPS is no longer in Stop
(Bypass) mode.
N/A