UPS Shutdown Events
RemotEye II can initiate output shutdown upon the occurrence of six different UPS
events, Input Power Failure, Low Battery, UPS Overload, UPS Over Temperature,
Recurring Schedule and Non-recurring Schedule. Users can view the current setting
of these events on UPS Shutdown Events page in UPS Management menu. To alter
these settings, log in as an administrator, and configure the UPS shutdown events
action and delay times accordingly. Click the Set Value button when finish. (See Pg.
61 for details)
Scenario:
Shutdown Event:
Status:
Delay (Min):
Warning Interval (sec):
UPS Output Shutdown Delay (Sec) 180(default)
UPS Events - AC failed
22 : 20 : 00
INVERTER
OUTPUT
SHUTDOWN
118
AC Failed
Client Shutdown
7 (default)
30 (default)
22:20:00
22 : 27 : 00
22 : 30 : 00