Action: Select from
None
Power On – Latch
Power On – Follow
Power Off – Latch
Power Off – Follow
Power Cycle
Times
Wait:
This is the length of time the iBoot-G2+ allows for a response to a ping.
With AutoPing operational, the main iBoot-G2 page will display the current status of this feature. The
status will be OK to indicate that iBoot-G2 is receiving responses to the ping, or that the fail counter has
not yet been exceeded.
If the fail count has been exceeded, the status will change to FAIL. The Trigger Counter indicates the
number of times the AutoPing action has been triggered. A counter reset button is provided.
Note:
All of the AutoPing Settings require a reboot of the iBoot-G2, after clicking Save. A Reboot button
will appear at the bottom of the page. The new settings will not take effect until the unit is
rebooted. Reboot will not affect the power position of the iBoot-G2. Upon Clicking Reboot, the
Goodbye page is displayed with a link to re-login.
7.5.
Event Scheduling
iBoot-G2 can schedule up to eight
reoccurring power events.
starting date and time, plus the action
to be taken and any repeat cycle for
each.
To enable the time scheduling
function:
Enter an accessible Network Time
Server and check the Enable box. A
list of public time servers is available
at
http://www.ntp.org/
time zone relative to GMT.
Once the time server is active, scheduled events can occur. Up to eight independent scheduled events
can be programmed.
Date: Set the initial date for the event. The format for the date is mm/dd/yyyy.
Time: Set the initial time for the event. The format for the time is hh:mm with hours in 24 hour format.
V130108E
AutoPing will not take any action upon Fail.
Upon triggering, iBoot-G2 will power on and remain so until changed via the
web, telnet, DxP, etc.
Upon triggering, iBoot-G2 will power on. When the ping response returns,
iBoot-G2 will power off.
Upon triggering, iBoot-G2 will power off and remain so until changed via the
web, telnet, DxP, etc.
Upon triggering, iBoot-G2 will power off. When the ping response returns,
iBoot-G2 will power on.
Upon triggering, iBoot-G2 will cycle the power. If Power Cycle does not
result in the ping response the iBoot-G2 can cycle again. The number of
times the iBoot-G2 will cycle is set by the Times setting. To have the iBoot
cycle power 3 times to get the system to respond again, set the Times to 3.
Set the
Set your local
iBoot-G2
Page 13