5.1 Technical Characteristics

SAFETY
RELAY
EMI FILTER
AC INPUT

5.2 Technical Specifications

OL1000RMXL2U / OL1500RMXL2U / OL2000RMXL2U / OL3000RMXL2U
Capacity (VA/W)
Operation Technology
Number of Phase
Voltage Range
Frequency Range
Input Power Factor
Number of Phase
Nominal Voltage
Voltage Regulation
Voltage T.H.D
5

Appendix

AC/DC PFC
CONVERTER
BATTERY
DC/DC
POWER
PUSH PULL
CHARGER
SUPPLY
BATTERY
OL1000RMXL2U: 1000/700
OL1500RMXL2U: 1500/1050
True On-Line & Double Conversion
AC Input
Single phase (1ψ2W+G)
60Vac~142Vac (Based on percentage of load)
40~70 ± 0.2Hz
≥ 0.95 @ Full load
AC Output
Single phase (1 ψ2W+G)
110 / 120 / 127Vac
± 3%
4% max @ Full linear load, 6% @ Full RCD load (9% max @
During last 30 seconds of backup time)
BYPASS
DC/AC
EMI FILTER
RELAY
INVERTER
OL2000RMXL2U: 2000/1400
OL3000RMXL2U: 3000/2100
Appendix 25
AC OUTPUT