Installation and test of the remote power off function
1. Check that the UPS is shut off and disconnected from the AC
power source.
2. Remove the RPO connector
3. Connect an insulated dry contact (NC, 60V DC, 30V AC max.,
20mA max., cable size 0.75mm) to the two terminals of the RPO
connector (B).
4. Put the RPO connector
5. Connect the UPS to the AC-power source and restart it
as indicated previously.
6. Activate the RPO external contact to test the function.
7. To return to normal operation, deactivate the RPO external contact
and restart the UPS using button
UPS, and press it again to restart the UPS).