1. INSTALLATION GUIDE INSTALLATION PLACE Indoor unit Outdoor unit • Flat and strong place in the room • A place no reach of direct ray of sun (if necessary, shield the • No obstacles in front of air in/out grille light) •...
INSTALLATION OF INDOOR UNIT 1) Drain hose should maintain downward slope to outside of room. 2) Indoor unit should be fixed firmly with the bracket to avoid falling down. The bracket has several holes to fix the unit any direction needed (fore/back/right/left) INSTALLATION OF OUTDOOR UNIT 1) Cushion rubbers absorb vibration of outdoor unit...
Spec Color 1.25mm BLUE SIGNAL LINE 1.25mm BLACK SIGNAL LINE 1.25mm SIGNAL LINE 1.25mm BROWN SIGNAL LINE 1.25mm BROWN MAIN POWER (INDOOR) 1.25mm YEL/GRN MAIN POWER (INDOOR) 1.25mm RED(or BLUE) MAIN POWER (INDOOR) 2.0mm BLACK MAIN POWER (OUTDOOR) 2.0mm YEL/GRN MAIN POWER (OUTDOOR) 2.0mm WHITE...
2. SPECIFICATIONS DPB-280LH MODEL DPB-280LH ITEM Function COOLING HEATING Class Power 220~240V/ 50Hz Capacity 8,200 8,200 Btu/h 28,000 28,000 Dehumidification Running Current Electrical Power Input 2,800 2,800 Data Starting Current Type Scroll Compressor Model ZR36K3-PFJ-501 Capacitor 50µF/370V AC Indoor Unit...
3. OUTLINE INDOOR UNIT DPB-280LH Part Name Quantity Description Remarks Connecting Hole ø60X100 (Left, Right, Back) Evaporator Heat Exchanger Suction Grille Air Inlet Discharge Grille Air outlet Fan Blower Sirocco Type Joint (Gas) OD ø15.88mm Joint (Liquid) OD ø9.52mm...
Page 8
OUTDOOR UNIT DPB-280LH Part Name Quantity Description Remarks Service Valve (Liquid) OD ø9.52mm Flare Type Service Valve (Gas) OD ø15.88mm Flare Type Service Door Fan Guard Fan Protector Fan Blower Propeller type Condenser Heat Exchanger Fan motor Foor propeller fan...
4. OPERATION PARTS OF NAME AND FUNCTION Indoor Unit AIR OUT - According to the operation mode, it is opened/closed automatically. MAIN CONTROLS/ REMOTE SENSOR AIR IN - It is to suck warm air. - There is an air filter inside this grille. •...
Page 10
ROOM TEMPERATURE / DESIRED TEMPERATURE INDICATOR - It displays current room temperature and desired room temperature. FAN MODE INDICATOR AUTO FAN SPEED INDICATOR AUTO MODE INDICATOR FAN SPEED INDICATOR COOL MODE INDICATOR TIMER/SLEEP INDICATOR QUICK MODE INDICATOR ECONOMY MODE INDICATOR MODE BUTTON HEAT MODE INDICATOR...
Outdoor Unit OUTDOOR UNIT AIR OUT SERVICE VALVES(GAS TUBE) SERVICE VALVES(LIQUID TUBE) CAUTION • Do not install the outdoor unit on OUTDOOR UNIT AIR IN unstable place like outside wall of - If there is any obstacle in front building or outside of balcony. In case of falling, it may cause serious trouble of the grille, the efficiency of and damage.
REMOTE CONTROLLER Name of Each Button Display AUTO Displays information pertaining to unit. ON/OFF Button Press to turn the unit on or off. TEMPERATURE Buttons Press to raise or lower FAN SPEED Button the desired temperature. Press to select the fan speed FAN DIR.
REMOTE CONTROLLER DISPLAY MODE Indicators (Auto/Quick/Cool/Fan/Dehumidifier/Heat) Lights to indicate the mode selected. AUTO FAN Indicators FAN DIRECTION Indicators Lights to indicate Lights to indicate the the fan speed. fan direction. NATURAL Indicator Lights to indicate the speeds simulating a breeze. TIMER Indicators Lights to indicate the timer function mode.
Page 14
DESCRIPTION OF FUNCTIONS OFF-Timer If you set time in OFF-Timer Mode, the unit will stop at the set time. Unit ON Unit OFF SET Time HOUR ON-Timer If you set time in ON-Timer Mode, the unit will run at the set time. Unit ON Unit OFF SET Time...
Page 15
Fan Speed (Indoor Unit) (1) Motor speed (high speed, middle speed, low speed). (2) Remote controller setting fan speed. (Auto, L, M, H, Natural) (3) Relation of operating mode between fan speed. (legned: X-no relation) DEHUMI- FAN ONLY COOL AUTO QUICK HEAT DIFICATION...
Sleep Mode (1) When you are going to sleep, select sleep switch and the unit controls the room to the desired temperature. (The unit will not operate after 4 hour) (2) For changing the temperature. +0.5 C +0.5 C –0.5 C +0.5 C –0.5 C –0.5 C...
3 min. Time Delay of Compressor In normal operation, there is a time delay of three minutes between turn off and turning back on including initial 3 Seconds Time Delay of Indoor Fan Motor When the speed of indoor fan motor changes, there is a time delay of 3 seconds at each speed step. Auto Mode (1) In Auto Mode After the indoor fan is operated for 20 seconds in the Auto Mode, the unit will operate automatically by selecting...
5. CIRCUIT DIAGRAM WIRE CONNECTION OF INDOOR AND OUTDOOR UNIT DPB-280LH...
Page 20
MAIN ELECTRIC PARTS DPB-280LH Object/part No. Manufacturer/trademark Type/model Technical data Standard Mark(s) of confirmity Motor-compressor Copeland ZR36K3-PFJ AC220-240V 50Hz R22 DEMKO Outdoor fan motor A2935BA010 AC 230V 50Hz NONE Indoor fan motor O-YANG DE112 AC 230V 50Hz NONE Thermal protector for...
PCB DRIVING DESCRIPTION Power Supply(1) AC 220V 275V 7812 7805 104K FUSE1 VI VO VI VO 3.15A 100 F 1000 F 470 F POWER TRANS DESCRIPTION DC Power Supply in circuit needs +12V and +5V. +12V is used for Compressor Driving Relay, Triac Driving Photo Triac, Buzzer Driving, Stepping Motor.
Page 25
Sensor(3) Room temperature and Evaporator temperature Sensor Input CN10 MICOM PT-K43C 12.7K Room SMW250-04 PT-K43C 12.7K DESCRIPTION Number 23 of Micom is Terminal of A/D convertor Input. Room temperature and Evaporator temperature is sensing by change of Thermister Resistance, Micom is put in 5V by ratio between R37 (12.7K ) and R38 (12.7K ).
Page 26
Triac Driving(4) AC 220V TLP561 130 H MICOM 0.1 F 120Ohm SM3JZ47 KID 65004 TO MOTOR 1/2W DESCRIPTION Number 32 Terminal of Micom is put out Pulse Output, by way of Buffer it is driving Photo Triac is supplied Trigger Signal. Trigger Test of Triac is detected Zero Cross Part of AC input and it is triggered from Zero Cross part to Time delay part according to Fan Speed.
Page 27
Remote Controller(5) DESCRIPTION Signal from Remote Controller put in only Control Data Signal at Micom Terminal of Number 33, which is gotten fid of Carrier (38KHz) from Receive Module. Signal Wave repeat third as following Fig 5-1. But in Secondary Wave Custom Code is Reversed Face. 4.5ms 16bit 24bit...
Page 28
Micom Power Supply(7) VDD 42 10 F MICOM 8MHz DESCRIPTION MICOM Power is supplied 5V at Number 42 using VDD, Number 19, 20 Using Oscillator, CC7 is noise filter.
Page 29
Reset(8) 5.6K 7042P 4.7 F MICOM DESCRIPTION Voltage less than about 0.8V put in Micom Terminal of Number 18 and then Micom reset. Reset IC detect Power ON and Voltage less than 4.25V, and then send Reset Signal. Vcc (+5V) 4.25V DELAY TIME FOR POWER ON...
Page 30
Function Selecting(9) MICOM DESCRIPTION Selecting function is as following table 9-1. When power source is put at first, Funtion selection input is recognized. And when the unit is running the microcomputer ignore variation of funtion selection input. SHORT OPEN SIMPLE MILD HIGH Heat Pump...
Page 31
Zero Crossing Detect(11) KRC102M MICOM TRANS OUTPUT 5.6K DESCRIPTION It detect Zero Cross part of Trans output voltage, Transistor TR2 is used to put in the Micom. Detail Driving is as following Fig 11-1. AC18V Number 31 of Micom terminal DETECT POINT Fig 11-1...
Page 32
Stepping Motor Driving(12) CN11 Ø 1 Ø 2 FOR SWING MICOM Ø 3 Ø 4 KID65004 DESCRIPTION There are one Stepping Motor for Flap (up and down) and it is used 4 face Drive Method. It is driving as following Fig 12-1. (Ring Count Method of 8 Status) Ø...
Page 33
MICOM Display Output P77(HSO) P76(HSCK) (XTOUT)P22 Key Input P75(SO) (XTIN)P21 P74(SI) (INT5/STOP)P20 P73(SCK) Compressor Heater Driving P72(PDO/PWM) P71(INT4) (TC2)P15 P70(INT3/TC3) (PPG)P14 Outdoor Unit Motor Driving Stepping Motor (DVO)P13 Buzzer Driving (INT2/TC1)P12 Remocon Input (INT1)P11 Indoor Unit Motor Driving (INTO)P10 Zero Crossing Detect (AIN7)P67 Display Driving Compressor Relay Driving...
Page 34
DARLINGTON ARRAYS (KID65004) IN1 1 16 OUT 1 IN2 2 15 OUT 2 COMMON IN 3 3 14 OUT 3 INPUT OUTPUT IN 4 4 13 OUT 4 10.5K‰ IN5 5 12 OUT 5 7.2K‰ IN6 6 11 OUT 6 IN7 7 10 OUT 7 GND 8...
6. REFRIGERANT CYCLE INDOOR UNIT OUTDOOR UNIT HIGH PRESSURE SWITCH INDOOR HEAT EXCHANGER UNION SERVICE VALVE FILTER OUTDOOR COMPRESSOR HEAT EXCHANGER DISTRIBUTER CAPILLARY TUBE Note) If the pipe length exceeds the standard length, add 30g of refrigerant per extra meter. Model Name Cooling Heating...
Trouble Is the Is the power Check power supply mains unit display applied to the or interconnection wires normal? unit Outdoor unit does Is the not run?(note. 1) power normal? check the voltage between Check the wiring of indoor L & N of terminal block Does the compressor run...
Neither Indoor Unit nor Outdoor Unit Runs The power is applied to the unit Rating voltage Check the Breaker or Fuse under 90% Check the voltage between of terminal block Rating voltage more than 90% Check the indoor unit display Self Diagnostic is the display all off? function is ON...
Page 39
Outdoor Unit Runs but Indoor Unit Do Not Run Check rotation of indoor fan Check the Fan Motor bearing and fan Rotate indoor fan by hand Check the power P.C.B. Rating voltage Check input Voltage of Fan Motor connector at power P.C.B under 90% The circuit for triac control Rating Voltage more than 90%...
Page 40
Outdoor Fan Do Not Run Rating voltage Check the voltage between Check the of outdoor unit terminal connecting wire under 90% Check the wiring Rating voltage Check the voltage between and voltage of indoor unit terminal under 90% within doors Rating voltage Check the Check the voltage between...
Page 41
Only Compressor Do not Run - Check the following at cooling mode Check the connecting Rating voltage Check the voltage between wire between indoor of outdoor unit terminal less than 90% and outdoor. Rating voltage more than 90% Check the control P.C.B Rating voltage Check the voltage between the circuit for relay...
Page 42
REMOTE CONTROLLER ASSMBLY FUNCTIONAL TEST METHOD TEST START Power supply again Power Supply Is Display at the beginning ON? Select ON/OFF button Check the Following BATTERY SPRING MICOM Is Display at the beginning ON? Select Mode button ERROR Is it normal? Select FAN SPEED button Is it normal? ERROR...
Page 43
ERROR Is LCD display OFF? Select TIMER ON Button ERROR Is it normal Select Timer Enter Button display? ERROR TIMER Select CANCEL Button ERROR Is all display OFF? Select ON/OFF Button Select OFF (Timer) Button (0.5~24 HOUR) ERROR Is it normal? Select SLEEP Button SLEEP MODE ERROR...
Page 46
Part Code Part Name Quantity Remarks 3100090100 ASSY CABNET BODY 3100042301 BASE MOTOR ASSY 3100602801 BRACKET PAN DRAIN 3108008600 MOTOR IDU 3101501900 CUSHION MOTOR 3106600210 SCROLL HOUSING 3106903100 CAPACITOR MOTOR IDU 3100025000 BLOWER ASSY 3105200300 WASHER STOPPER 3100301600 BASE 3101501100 CUSHION BASE 3100503901 BOX CONTROL...
Page 47
Part Code Part Name Quantity Remarks 3100604800 BRACKET FRONT R 3102201600 FRAME DISCHARGE 310P40086E SWING MOTOR ASSY 3108005300 MOTOR STEPPING 3101101300 CASE MOTOR 3100702100 BUSHING MOTOR 3106501430 BLADE HORIZONTAL 1 3106501530 BLADE HORIZONTAL 2 3107801000 LINK GUIDE R 3107802200 LINK M 3106700100 3106301100 BAR VERTICAL...