6. REFRIGERANT CYCLE

INDOOR UNIT
INDOOR
HEAT EXCHANGER
FAN
M
Note) If the pipe length exceeds the standard length, add 30g of refrigerant per extra meter.
Model Name
Contents
Capillary tube
L
Charge Quantity
UNION
FILTER
DISTRIBUTER
CAPILLARY TUBE
Cooling
IDØ1.4 x 1000mm(6.0l/min) x 5EA
35
OUTDOOR UNIT
M
SERVICE VALVE
OUTDOOR
HEAT EXCHANGER
Heating
ODØ2.0 x 250mm
2000 g
HIGH PRESSURE SWITCH
COMPRESSOR