Briggs & Stratton 040336-00 Operator's Manual page 35

Home generator system
Hide thumbs Also See for 040336-00:
Table of Contents

Advertisement

Available languages

Available languages

15k Watt (California Only)
Rated Maximum Load Current* (at 25°0/77°F, LP)*:
at 240 Volts .......................................................62.5 Amps
Rated AC Voltage............................................. 120/240 Volts
Phase................................................................. Singb phase
Rated Frequency.......................................................60 Hertz
Generator Breaker......................................................80 Amp
Normal Operating Range._ o25°F(-28.8°0) to 104°F (40°0)
Output Sound Level69.1 dB(A) at 23 ft. (7 m) at normal load
Shipping Weight ............................................565 Ib (256 kg)
* Naturalgas ratingwill dependon specificfuel but typical@ratesare between 10 to
20% off the LP gas rating.
Displacement............................................. 60.60 ci. (993 cc)
Bore ....................................................... 3.405 in. (86.5 mm_
Stroke ....................................................3.366 in. (85.5 mm_
Spark Hug Gap...................................... 0.020 in. (0.51 mm}
Spark Hug Torque.................................... 180 Ib-in. (20 Nm_
Armature Air Gap............ 0.005 o 0.008 in. _&13 - 0.20 mm_
intake Valve Clearance.... 0.004 o 0.006 in. _&lO - 0.15 mm_
Exhaust Valve Clearance.0.004 o 0.006 in. t0.10 - 0.15 mm}
Oil Type......................................................... 5W30 Synthetic
Oil Capacity
(with filter) ......................
78 - 80 oz. (2.3 - 2.4 L_
Engine End Cover Bolt ............................... 220 Iboin(25Nm_
Air Filter
842856
Oil o- Synthetic
100074
Oil Filter
842921
Resistor Spark Hug
692051
Long Life Platinum Spark Hug
5066
Maintenance Kit
6036