Initial UPS Startup

The first time the UPS is activated after being shipped from the factory, an initialization program will require the
operator to input the following parameters. The UPS display operation is explained in detail on pages 32-62
1.
The first screen during the initial startup sequence requires the operator to select the nominal input voltage.
Select from 208V, 230V, or 240V, and press the Write key. If the command has been accepted, the word
"Successful" will appear at the bottom left side of the display.
2.
Repeat the process in step 1 in selecting the
3.
Repeat the process in step 1 in selecting the
4.
Use the keypad to type in the
5.
Use the keypad to type in the
6.
The Main screen is now displayed. Verify the UPS is in
display) should display Bypass. If it does not display Bypass, press and momentarily hold the STOP button.
7.
With the UPS in bypass mode, cycle power to the UPS as follows:
At the rear of the UPS switch the main circuit breaker MCCB to OFF.
Leave the UPS off until the DC bus is safely discharged (approximately 5-10 minutes).
Restart the UPS by switching the main circuit breaker ON.
The table below summarizes the initialization parameters:
ID
Command
111
Rated Vin
215
Rated Vout
141
Input Frequency
634
UPS Date
635
UPS Time
FAQ Sheet
Following are some Frequently Asked Questions concerning installation of the 1600EP Series UPS.
The batteries for the UPS must be installed while the UPS is energized.
NOTICE
FAQ #1
My Output is ~85V.
Problem: Output is wired across the incorrect output terminals. The voltage across terminals 5 – 6(X2 – N) will
be approximately 85V.
Solution: The correct 120V output terminals are 4 – 6 (X1 – N), and 7 – 6 (X3 – N).
FAQ #2
My Output is other than 85, 120, 208 or 240V.
Problem: The Terminal strip jumper may be installed incorrectly for the incoming voltage.
Solution: Check that the Jumper wire/buss strip is installed correctly for the incoming voltage.
Toshiba Contact Information: Toshiba Industrial Division, 13131 West Little York Road, Houston, TX 77041
Tel: US 800-231-1412, Canada 800-872-2192, Mexico 01/800/527-1204
4
4
Rated Vout.
Input Frequency.
current date in the format: Mon 10/05/2009. and press Write.
current time in 12 hour format: 12:15 PM and press Write.
Select from 208V, 230V, or 240V, and press Write.
Select from 208V, 230V, or 240V, and press Write.
Select from 60Hz or 50Hz, and press Write.
Input the date in this format: Mon 10/05/2009. and press Write.
Input the current time in 12 hour format: 12:15 PM and press Write.
BYPASS mode. The mode (lower right side of the