Electrical.wiring.for.265.Volt.models - Friedrich 920-087-09 (12/10) Installation And Operation Manual

Packaged terminal air conditioners & heat pumps
Table of Contents

Advertisement

Model
PDE07K
PDE/PDH07K
PDE09K
PDE/PDH09K
PDE12K
PDE/PDH12K
PDE15K
PDE/PDH15K
PDE/PDH07R
PDE/PDH09R
PDE/PDH12R
PDE/PDH15R
Electrical Wiring for 265 Volt
Models
Power Cord Installation
All.265V.PTAC/PTHP.units.come.with.a.factory.installed.non-LCDI.
power.cord.for.use.in.a.subbase..If.the.unit.is.to.be.hard-wired.refer.to.
the.instructions.below.
NOTE:.
It. is. recommended. that. the. PXSB. subbase. assembly,. the.
PXCJA.conduit.kit.(or.equivalent).be.installed.on.all.hardwire.
units...If.installing.a.flush-floor.mounted.unit,.make.sure.the.
chassis. can. be. removed. from. the. sleeve. for. service. and.
maintenance.
WARNING
Electrical Shock Hazard
Turn off electrical power before service
or installation.
ALL electrical connections and wiring
MUST be installed by a qualified
electrician and conform to the National
Code and all local codes which have
jurisdiction.
Failure to do so can result in property
damage, personal injury and/or death.
14
Heater kW
Power Cord Kit
0.0
PXPC23000
2.0
PXPC23015
3.0
STD
0.0
PXPC23000
2.0
PXPC23015
3.0
STD
5.0
PXPC23030
0.0
PXPC23000
2.0
PXPC23015
3.0
STD
5.0
PXPC23030
0.0
PXPC23000
2.0
PXPC23015
3.0
PXPC23020
5.0
STD
2.0
PXPC26515
3.0
STD
2.0
PXPC26515
3.0
STD
5.0
PXPC26530
2.0
PXPC26515
3.0
STD
5.0
PXPC26530
2.0
PXPC26515
3.0
PXPC26520
5.0
STD
TABLE 2
Voltage
230/208
230/208
230/208
230/208
230/208
230/208
230/208
230/208
230/208
230/208
230/208
230/208
230/208
230/208
230/208
265
265
265
265
265
265
265
265
265
265
265
To install the line voltage power leads and conduit
to chassis, follow the instructions below and refer
to Figures 25-27 on page 19. PXCJA Conduit Kit
is required with this setup.
1. Follow. the. removal. process. of. the. chassis's. junction. box. .
(Figure.25,.step.2,.page.19).
2. . P repare.the.265V.(or.230V).power.cord.for.connection.to.the.chas-
sis'.power.cord.connector.by.cutting.the.cord.to.the.appropriate.
length.(refer.to.Figure.26.and.follow.Figure.15)...Power.cord.harness.
selection.shown.on.Table.2.on.page.14.
Amperage
Receptacle
15
NEMA.6-15r
15
NEMA.6-15r
20
NEMA.6-20r
15
NEMA.6-15r
15
NEMA.6-15r
20
NEMA.6-20r
30
NEMA.6-30r
15
NEMA.6-15r
15
NEMA.6-15r
20
NEMA.6-20r
30
NEMA.6-30r
15
NEMA.6-15r
15
NEMA.6-15r
20
NEMA.6-20r
30
NEMA.6-30r
15
NEMA.6-15r
20
NEMA.6-20r
15
NEMA.6-15r
20
NEMA.6-20r
30
NEMA.6-30r
15
NEMA.6-15r
20
NEMA.6-20r
30
NEMA.6-30r
15
NEMA.6-15r
20
NEMA.6-20r
30
NEMA.6-30r

Advertisement

Table of Contents
loading

Table of Contents