Honeywell VisionPRO 8000 Product Data page 17

8000 series touchscreen programmable thermostat
Hide thumbs Also See for VisionPRO 8000:
Table of Contents

Advertisement

Installer Setup
Number
Installer Setup Name
0260
Cycles per hour (cph) for
3rd Stage Heat
(Aux Heat for 3H/2C
Heat Pumps)
0270
Cycles per hour (cph) for
Em Heat
0280
Continuous Backlight
0300
Changeover
0310
Deadband
0320
Temperature Indication
Scale
0330
Daylight Savings
0340
Remote Temperature
Sensor (Outdoor or
Indoor)
0350
Heat Pump Compressor
Lockout or (Balance
Point)
VisionPRO
Table 3. Installer Setup Menu. (Continued)
Settings
1—1 cph used for steam and gravity
3—3 cph for hot water systems and high efficiency (90%
or better) furnaces
5—5 cph for standard fossil fuel forced air (less than 90%
efficient) systems (factory setting)
9—9 cph used for electric furnaces or electric auxiliary
heat for heat pump systems
2, 4, 6, 7, 8, 10, 11, 12—other cycle rate settings
3—3 cph for hot water systems and high efficiency (90%
or better) furnaces
5—5 cph for standard fossil fuel forced air (less than 90%
efficient or better) systems
9—9 cph for electric strip heat for heat pumps
0—Backlight not on continuously. Thermostat backlight
comes on with each key press.
1—Backlight is on continuously (thermostat must have a
common wire attached for this function).
0—manual changeover (factory setting)
1—auto changeover
Heating and cooling setpoints can be set no closer than
chosen value:
°
°
2—2
F (1.5
C)
°
°
3—3
F (2
C)
°
°
4—4
F (2.5
C)
°
°
5—5
F (3
C)
°
°
6—6
F (3.5
C)
°
°
7—7
F (4
C)
°
°
8—8
F (4.5
C)
°
°
9—9
F (5
C)
0—fahrenheit temperature display (factory setting)
1—celsius temperature display
1—daylight savings is on (factory setting).
0—daylight savings is off.
0—no remote temperature sensor
1—outdoor temperature sensor for display only.
2—outdoor temperature sensor for control. Outdoor
sensor used for Heat Pump Lockout settings. (See Heat
Pump Temperature Lockout section for more details.)
3—indoor temperature sensor
0—no compressor lockout.
°
°
15
F (-9.5
C)
°
°
20
F (-6.5
C)
°
°
25
F (-4
C)
°
°
30
F (-1
C)
°
°
35
F (1.5
C)
°
°
40
F (4.5
C)
°
°
45
F (7
C)
17
TM
8000 Touchscreen Programmable Thermostat
Only shown if 3H/2C
heat pump is selected.
Only shown if 2H/1C or
3H/2C heat pump is
selected.
Option is always shown;
however, continuously on
backlight works only if
thermostat is wired with
24 Vac Common.
Shown only if automatic
changeover is selected.
Set to 0 in areas that do
not follow daylight
savings.
Defaults and Options
depend on System Type
selection.
Indoor Temperature
Sensor uses an averaging
network and does not
include on-board sensor.
Default depends on other
selections. Shown if
Outdoor Temperature for
control is selected. (See
Advanced Features
section for more
information.)
Notes
68-0280—01