TM
VisionPRO
8000 Touchscreen Programmable Thermostat
Installer Setup
Number
Installer Setup Name
0120
Date (Year Upper)
0130
Date (Year Lower)
0140
Date (Month)
0150
Date (Day)
0160
Schedule Options
0170
System Type Selection
0180
Fan Control in Heating
0190
Changeover Valve—O/B
Terminal Energized in
Heating or Cooling
(Heat Pumps Only)
0200
Backup Heat Source
(Auxiliary Heat)
0210
External Fuel Fossil
Fuel Kit
0220
Cycles per hour (cph) for
1st Stage Compressor
0230
Cycles per hour (cph) for
2nd Stage Compressor
0240
Cycles per hour (cph) for
1st Stage Conventional
Heat
0250
Cycles per hour (cph) for
2nd Stage Heat (Aux
Heat for 2H/1C Heat
Pumps)
68-0280—01
Table 3. Installer Setup Menu.
Settings
Select first two digits of current calendar year (2005, etc) 2001 - 2178 available
Select last two digits of current calendar year (05 for year
2005, etc)
Select number that represents current calendar month
Select number that represents current calendar date
0—nonprogrammable
4—7-day programmable
1—1 heat/1 cool conventional (factory setting)
2—single-stage heat pump (no auxiliary heat)
3—heat only conventional (no fan) Also for 750mV.
4—heat only conventional (with fan)
5—heat only (power to open and power to close zone
valves or normally-open zone valves)
6—cool only conventional
7—2 heat/1 cool heat pump (with auxiliary heat)
8—2 heat/2 cool multistage conventional
9—2 heat/1 cool multistage conventional
10—1 heat/2 cool multistage conventional
11—2 heat/2cool heat pump (no auxiliary heat)
12—3 heat/2cool heat pump (with auxiliary heat)
0—gas or oil furnace equipment controls fan in heating
(factory setting)
1—electric furnace—thermostat controls fan in heating
0—changeover valve—O/B terminal is energized in
cooling (factory setting)
1—changeover valve—O/B terminal is energized in
heating
0—heat pump backup heat source is electric (factory
setting)
1—heat pump backup heat source is fossil fuel
0—no external fossil fuel kit is controlling heat pump
backup heat. This thermostat controls the dual fuel. Must
install outdoor sensor and set Installer Setup Number
0340 to number 2.
1—external fossil fuel kit is controlling heat pump backup
heat
3—cph recommended for compressors (factory setting)
1, 2, 4, 5, 6—other cycle rate settings
3—cph recommended for compressors (factory setting)
1, 2, 4, 5, 6—other cycle rate settings
1— 1 cph used for steam and gravity
3—3 cph used for hot water system and high efficiency
(90% or better) furnaces
5—5 cph used for standard fossil fuel forced air (less than
80% efficient) systems (factory setting)
9—9 cph used for electric furnaces
2, 4, 6, 7, 8, 10, 11, 12—other cycle rate settings
1—1 cph used for steam and gravity
3—3 cph for hot water systems and high efficiency (90%
or better) furnaces
5—5 cph for standard fossil fuel forced air (less than 90%
efficient) systems (factory setting)
9—9 cph used for electric furnaces or electric auxiliary
heat for heat pump systems
2, 4, 6, 7, 8, 10, 11, 12—other cycle rate settings
16
Notes
2001 - 2178 available
Available options and
defaults vary by
thermostat. System
selection automatically
modifies some default
settings and/or hides
other Installer Setup
options.
Only shown if
conventional system is
selected. If heat pump is
chosen, fan defaults to
electric.
Only shown if heat pump
system is chosen.
Only shown if 2 heat/
1 cool or 3 heat/2 cool
heat pump is chosen
Only shown if fossil fuel is
chosen as backup heat
source.
Only shown if two stages
of cool are selected.
Not shown if system
selection is heat pump.
Selection in this stage
changes default cph for
2nd stage heat.
Only shown if two stages
of heat are selected.