Electrical Data - Trane RTAA-70 Installation & Maintenance Manual

R series air-cooled rotary liquid chillers
Table of Contents

Advertisement

Table 10

Electrical Data

Rotated
Unit Size
Voltage MCA (2) MOP (1)
RTAA 70
200/60
300
230/60
265
460/60
133
575/60
108
346/50
153
400/50
133
RTAA 80
200/60
361
230/60
319
460/60
160
575/60
131
346/50
184
400/50
160
RTAA 90
200/60
428
230/60
378
460/60
190
575/60
154
346/50
243
400/50
214
RTAA 100
200/60
483
230/60
426
460/60
214
575/60
173
346/50
243
400/50
214
RTAA 110
200/60
536
230/60
471
460/60
235
575/60
191
346/50
270
400/50
236
RTAA 125
200/60
576
230/60
507
460/60
253
575/60
205
346/50
291
400/50
253
(1) MOP - Maximum Overcurrent Protection - may be either type breaker (UL/CSA) or with circuit breakers (CSA only). MOP = 225 percent of the largest
compressor RLA plus 100 percent of the second compressor plus the sum of the condenser fans FLAs per NEC 440-22.
(2) MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of second compressor plus the sum of the condenser
fans FLAs per NEC 440-33.
(3) RECOMMENDED TIME DELAY OR DUAL ELEMENT (RDE) FUSE SIZE: 150 percent of the largest compressor RLA plus 100 percent of the
second compressor RLA and the sum the condenser fan FLAs.
(4) RLA -Rated Load Amps -rated in accordance with UL Standard 465.
(5) Local codes may take precedence.
(6) Control kw includes operational controls only. Does not include heat tapes.
(7) LRA - Locked Rotor Amps -based on full winding start units.
(8) VOLTAGE UTILIZATION RANGE:
Rated Voltage
200/60
230/60
460/60
575/60
400/50
(9) 60 HZ UNITS - A 115/60/1, 15 amp. customer provided power connection is required to power the evaporator heat tape 420 watts
(10) 50 HZ UNITS - A separate 220/50/1 15 amp. customer provided power connection is needed to power evaporator heat tape 420 watts @ 220 volts.
50
Installation — Electrical
Unit Wiring
Rec Time
Delay or
RDE (3)
400
350
350
300
175
150
125
125
200
175
175
150
500
400
400
350
200
175
175
150
250
225
200
175
600
600
500
500
250
225
200
175
300
250
250
225
600
600
500
500
250
250
225
200
300
300
250
250
700
600
600
600
300
300
250
225
350
300
300
300
800
700
700
600
350
300
250
225
400
350
350
300
Utilization Range
180-220
208-254
414-506
516-633
340-460
Motor Data
Compressor
Qty.
(Ea) RLA (4) LRA (7)
2
115/115
800/800
2
100/100
690/690
2
50/50
330/330
2
40/40
270/270
2
58/58
390/390
2
50/50
325/325
2
142/142
800/800
2
124/124
760/760
2
62/62
380/380
2
50/50
304/304
2
72/72
430/430
2
62/62
375/375
2
192/142
990/880
2
167/124
820/760
2
84/62
410/380
2
67/50
328/304
2
96/72
485/430
2
84/62
402/375
2
192/192
990/990
2
167/167
820/820
2
84/84
410/410
2
67/67
328/328
2
96/96
485/485
2
84/84
402/402
2
233/192
1190/990
2
203/167
1044/820
2
101/84
522/410
2
81/67
420/328
2
117/96
585/485
2
101/84
512/402
2
233/233
1190/990
2
203/203
1044/1044 10
2
101/101
522/522
2
81/81
420/420
2
117/117
585/585
2
101/101
512/512
Fans (Ea)
Control
Qty.
KW
FLA
KW (6)
8
1.0
5.1
0.75
8
1.0
5.0
0.75
8
1.0
2.5
0.75
8
1.0
2.2
0.75
8
1.0
2.7
0.75
8
1.0
2.5
0.75
8
1.0
5.1
0.75
8
1.0
5.0
0.75
8
1.0
2.5
0.75
8
1.0
2.2
0.75
8
1.0
2.7
0.75
8
1.0
2.5
0.75
9
1.0
5.1
0.75
9
1.0
5.0
0.75
9
1.0
2.5
0.75
9
1.0
2.2
0.75
9
1.0
2.7
0.75
9
1.0
2.5
0.75
10
1.0
5.1
0.75
10
1.0
5.0
0.75
10
1.0
2.5
0.75
10
1.0
2.2
0.75
10
1.0
2.7
0.75
10
1.0
2.5
0.75
10
1.0
5.1
0.75
10
1.0
5.0
0.75
10
1.0
2.5
0.75
10
1.0
2.2
0.75
10
1.0
2.7
0.75
10
1.0
2.5
0.75
10
1.0
5.1
0.75
1.0
5.0
0.75
10
1.0
2.5
0.75
10
1.0
2.2
0.75
10
1.0
2.7
0.75
10
1.0
2.5
0.75
RTAA-SVX01A-EN