Electrical Data - Trane Cold Generator CICD Series Installation, Operation And Maintenance Manual

Compact chiller 30 to 75 tons (60 hz), r-410a
Table of Contents

Advertisement

Electrical Data

Table 2.
Electrical data
Size
Rated Voltage
200-230/60/3
30
460/60/3
575/60/3
200-230/60/3
45
460/60/3
575/60/3
200-230/60/3
55
460/60/3
575/60/3
200-230/60/3
65
460/60/3
575/60/3
200-230/60/3
75
460/60/3
575/60/3
Notes:
1. Use copper conductors only.
2. Local codes may take precedence.
3. Voltage Utilization Range: ± 10% of rated voltage. Rated voltage (use range): 200-230/60/3 (180-253), 460/60/3 (414-506), 575/60/3 (517-632).
10
Compressor
# of
Refrigerant
Nominal
Qty
Circuits
Tons
2
1 or 2
15/15
2
1 or 2
20/20
2
1 or 2
25/25
2
1 or 2
32/32
2
1 or 2
35/35
Minimum
RLA
LRA
Circuit
(each)
(each)
Ampacity
48
351
109
25
197
56
22
135
51
67
485
153
33
215
74
26
175
60
82
560
186
40
260
90
29
210
65
109
717
246
51
320
115
38
235
87
103
635
233
51
316
116
41
258
93
Wiring
Max
Fuse
Recommended Dual
Size
Element Fuse Size
150
110
80
60
70
60
200
200
100
80
80
60
250
200
125
90
90
70
350
250
150
125
125
90
300
250
150
125
125
110
CG-SVX044B-EN