Trane RTAA-70 Installation & Maintenance Manual page 133

R series air-cooled rotary liquid chillers
Table of Contents

Advertisement

Table 19
Diagnostic Codes
Diagnostic Description
Tracer Communications Loss
Under Voltage
U1 Indicating U2 Communications
U1 Indicating U3 Communications
U1 Indicating U4 Communications
U1 Indicating U5 Communications
U1 Indicating U6 Communications
U1 Indicating U7 Communications
U3 Indicating U1 Communications
U3 Indicating U4 Communications
U3 Indicating U5 Communications
U3 Indicating U6 Communications
U3 Indicating U7 Communications
U4 Indicating U1 Communications
U4 Indicating U3 Communications
U4 Indicating U5 Communications
U5 Indicating U1 Communications
U5 Indicating U3 Communications
U5 Indicating U4 Communications
U6 Indicating U1 Communications
U6 Indicating U3 Communications
U6 Indicating U7 Communications
Winding Temp - Cprsr A
RTAA-SVX01A-EN
Diagnostics
Type
Cause
IFW
a.
b.
NOTE:
the positions of the chiller switch which account for
other chiller modes.
MAR
Line voltage below - 10% of nominal or the Under/Over trans-
former is not connected. (Must hold = -10% of nominal. Must
trip = -15% of nominal. Reset differential = min. of 2% and
max. of 4%. Time to trip = min. of 10 sec. and max. of 20 sec.)
Design: Nom. trip: 15 seconds at less than 87 .5%. ± 2.8% at
200V. or ± 1.8% at 575V, Auto reset at 90.5% or greater.
IFW
The 1U1 has det. a loss of IPC comm from the 1U2 module.
MMR
The 1U1 has det. a loss of IPC comm from the 1U3 module.
CMR
The 1U1 has det. a loss of IPC comm from the 1U4 module.
CMR
The 1U1 has det. a loss of IPC comm from the 1U5 module.
CMR
The 1U1 has det. a loss of IPC comm from the 1U6 module.
CMR
The 1U1 has det. a loss of IPC comm from the 1U7 module.
MMR
The 1U3 has det. a loss of IPC comm from the 1U1 module.
CMR
The 1U3 has det. a loss of IPC comm from the 1U4 module.
CMR
The 1U3 has det. a loss of IPC comm from the 1U5 module.
CMR
The 1U3 has det. a loss of IPC comm from the 1U6 module.
CMR
The 1U3 has det. a loss of IPC comm from the 1U7 module.
CMR
The 1U4 has det. a loss of IPC comm from the 1U1 module.
CMR
The 1U4 has det. a loss of IPC comm from the 1U3 module.
CMR
The 1U4 has det. a loss of IPC comm from the 1U5 module.
CMR
The 1U5 has det. a loss of IPC corn from the 1U1 module.
CMR
The 1U5 has det. a loss of IPC corn from the 1U3 module.
CMR
The 1U5 has det. a loss of IPC comm from the 1U4 module.
CMR
The 1U6 has det. a loss of IPC comm from the 1U1 module.
CMR
The 1U6 has det. a loss of IPC comm from the 1U3 module.
CMR
The 1U6 has det. a loss of IPC comm from the 1U7 module.
CMR
a.
b.
c.
While the chiller switch was in AUTO/REMOTE the
communications between the CSR and the connected
remote device, e.g., a Tracer or Remote Display, had
either never been established for more than 15 minutes
after power up or had been lost for more than 15
minutes after it had been established; use the Front
Panel Setpoints and the Default Chiller Auto/Stop.
In AUTO/LOCAL communications had been established
and was then lost for more than 15 minutes. Regardless
of the remote communications status the UCM uses
Front Panel setpoints.
The active modes for this diagnostic follow
The motor winding temperature thermostat opened;
nominally 221 F .
The motor temp. thermostat or wiring is open.
Time to trip from input open to compressor shutdown
shall be 0.5 to 2.0 seconds.
133