Oil Filter Change; System Oil Level Specifications - Trane RTAA-70 Installation & Maintenance Manual

R series air-cooled rotary liquid chillers
Table of Contents

Advertisement

RTAA-SVX01A-EN
Maintenance
4. After the level has been determined, remove the sight glass and hoses.
Figure 39

System Oil Level Specifications

Oil Filter Change

NOTE: Routine changing of the oil or the oil filter is not recommended. The
oil filter is oversized for this application and should not require replacement.
The oil and filter should be replaced only if analysis reveals that the oil is
contaminated. Oil type and system capacities are shown in
Pressure drops across the oil filter are shown in
drop is the difference between the pressure at the oil filter cover plate
Schrader valve and the pressure at the compressor oil supply Schrader valve,
on top of the compressor.
To change the oil filter in the unit, refer to
below.
1. Shut off the compressor and disconnect all electrical service to the com-
pressor.
2. Connect manifold gauge sets to the backseat ports of the suction and dis-
charge service valves and the Schrader valve on the oil filter cover plate.
3. Frontseat the suction and discharge service valves. Separate the Aero-
quip valve coupling, or close valve at the oil supply to the compressor or,
on later chillers, frontseat the oil supply line angle valve.
4. Recover refrigerant from the three connections in Step 2.
NOTE: The Schrader valve may have a high quantity of oil.
WARNING
Components Under High Pressure!
Failure to relieve pressure before removing filter retaining bolt
could result in death or serious injury
Table
Figure
41. Oil filter pressure
Figure 40
and follow the steps listed
1.
121

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rtaa-125Rtaa-80Rtaa-90Rtaa-100Rtaa-110

Table of Contents