Table 22. Manual output test sequence for 2-heat/2-cool configurations
1
Begins test mode
2
1
Fan on
3
Compressor 1
4
Compressor 2
5
Heat 1
6
Heat 2
7
Outdoor air damper
8
Generic/exhaust fan/occupancy
9
2
Exit
1
At the beginning of Step 2, the controller attempts to clear all diagnostics.
2
This step exits the manual output test and initiate a reset to restore the controller to normal operation.
Table 23. Manual output test sequence for 4-cool configurations
1
Begins test mode
2
1
Fan on
3
Compressor 1
4
Compressor 2
5
Compressor 3
6
Compressor 4
7
Outdoor air damper
8
Generic/exhaust fan/occupancy
9
2
Exit
1
At the beginning of Step 2, the controller attempts to clear all diagnostics.
2
This step exits the manual output test and initiate a reset to restore the controller to normal operation.
CNT-SVX12C-EN
Off
Off
Off
On
Off
Off
On
Off
On
On
Off
On
On
Off
Off
On
Off
Off
On
On
Off
On
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
Off
On
Off
On
On
Off
On
On
Off
On
On
Off
On
On
On
Off
On
Off
Off
Off
Off
Off
Service Pin button
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
Off
Off
On
Off
Off
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
Off
On
On
Off
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
75