Chapter 7 Applications for the heat pump configuration
52
tion.) The sensor communicates a value of 0–100% to the BAS. This con-
figuration has no direct effect on Tracer ZN517 operation.
For the CO
measurement configuration, a 4–20 mA sensor must be hard-
2
wired to the AI1 terminal as shown in Figure 16. The sensor will transmit
a 0–2000 ppm value to the BAS. This configuration has no direct effect on
Tracer ZN517 operation. If a valid value is established and then is no
longer present, the controller generates a CO
Figure 16. AI1 terminal wiring: CO
Tracer ZN517
CO
sensor
2
(Trane part number:
4190 4100 or 4190 4101)
For the RH measurement configuration, a hard-wired 4–20 mA zone
humidity sensor (see Figure 17) must provide a value to the controller. If
a valid hard-wired or communicated relative humidity value is estab-
lished and then is no longer present, the controller generates a RH Sensor
Failure diagnostic and disables the dehumidification function. The RH
sensor is used only to provide a valid humidity reading to a BAS; it does
not affect the operation of the Tracer ZN517.
Figure 17. AI1 terminal wiring: RH measurement
Figure Note:
The +20 terminal provides 20 ±2 Vdc that is used to power a Trane RH sensor (part
numbers 4190 1109, 4190 7011, 4190 7012, 4190 7014).
Sensor Failure diagnostic.
2
measurement
2
AI1
GND
+20
24 Vac
Out
24 Vac
GND
GND
+20
AI1
RH sensor
+
Tracer ZN517
CNT-SVX12C-EN