Trane Tracer ZN521 Installation And Operation Manual page 41

Zone controller
Hide thumbs Also See for Tracer ZN521:
Table of Contents

Advertisement

Occupancy (open=occupied)*
Condensate overflow (closed=normal)*
Low-coil-temperature detection
(closed=normal)*
H
24 Vac
N
LonTalk
CNT-SVX07C-EN
Figure 15. Two-pipe heating unit with face-and-bypass damper
Fan status (closed=on)*
Entering water
temperature
Discharge air
temperature
Wiring requirements and options
24 V
Fan, high speed
24 V
Exhaust (or fan, medium speed)
24 V
Fan, low speed
24 V
Face & bypass damper actuator
24 V
Heat isolation valve, open/close
24 V
Outdoor air damper actuator
AI4 input: See
Figures 5 and 6
on page 20 for
wiring options
Outdoor air or
generic temperature
* All binary inputs are configurable.
Connect 24 V to an AC POWER (24V) terminal.
24 V
Generic/baseboard heat
LonTalk
in
out
31