Other Alarm Indicators - Trane AdaptiView Operation Manual

For gear-driven water-cooled centravac (cvgf) chillers
Table of Contents

Advertisement

Alarms
alarms. Non-latching alarms change from the active to the historic state automatically, after the
problem has been resolved.
The Alarms screen does not directly state whether the alarms are latching or non-latching.
However, their behavior indicates their type:

Other Alarm Indicators

In addition to the Alarms screen, there are two buttons that indicate alarm conditions. These
buttons are viewable from any screen on the display. You can touch either one to access the Alarms
screen.
18
Reset latching alarms by touching the Reset Alarms button at the top of the Alarms screen
(Figure 6, p.
16). Latching alarms respond by disappearing from the active alarms list and
becoming a part of the historic alarms list. However, if the condition that caused the alarm
persists, the alarm will re-appear in the active alarms list.
You do not have to reset non-latching alarms. Non-latching alarms automatically disappear
from the active alarms list and re-appear in the historic alarms list when the conditions that
caused them are resolved.
The Alarms button in the main menu area of the screen
represents the alarm level of the most severe active alarm. The three color possibilities
correspond to those of the active alarm icons shown in
If an active alarm is present, the alarm indicator button
of the screen, as in
Figure 6, p.
active alarm.
16. The icon on this button indicates the level of the most severe
(Figure 1, p.
7) flashes a color that
Table 4, p.
17.
(Table 1, p.
8) appears in the upper left
CTV-SVU02A-EN