high or not
b. Cellar too large
c. Ambient temperature too high
cooling and
d. Exhaust restricted
running
continually
e. Malfunctioning fans
f.
g. Dirty Condenser
h. Iced evaporator
i.
j.
k. Undercharge or overcharge
l.
a. Improper cellar insulation & seal
7. Unit running
too long
b. Exhaust restricted
c. Cellar too large
d. Ambient temperature higher >
e. Dirty Condenser
f. Improper condenser air flow
a. Incorrect or loose wirings
8. Condenser
b. Failed components
fan running
but
c. Liquid
compressor
not running
a. Fan blade stuck
9. Compressor
b. Incorrect or loose wirings
running but
c. Failed motors
condenser
d. Fan cycle control
fan not
running
a. Failed components
10.Temperature
high,
b. Improper condenser airflow
compressor
c. Dirty condenser
stopping
d. Overcharge of refrigerant
and starting
e. Discharge or suction pressure
but very
short
running time
a. Post-compressor
11.Evaporator
fan running
too long
12. Evaporator
Evaporator or condenser airflow
Refrigeration system restriction
Refrigerant leak
Failed components
°
90
F
refrigerant
compressor
too high
fan
mode for humidity modulation
a. Incorrect or loose wirings
- 12 -
b. Check for excessive size
c. Check installation location
d. Leave minimum 3 feet clearance for
the hot air exhaust side and leave
minimum 1 foot clearance for the
ambient air intake side
e. Check for both evaporator and
condenser fans
f.
Check for air restrictions, air short-
circulation, grille directions
g. Clean condenser
h. Defrost and reset temperature
i.
Call service
j.
Call service
k. Call service
l.
Check compressor windings, start
relay and overload protector
a. Check insulation, gasket and door
opening
b. Leave minimum 3 feet clearance for
the hot air exhaust side and leave
minimum 1 foot clearance for the
ambient air intake side
c. Check for excessive size
d. Check for installation location
e. Clean condenser
f. Check
for
circulation
a. Check all wirings and connections
b. Check start relay, start capacitor,
overload protector, compressor.
in
the
c. Call service.
a. Check for proper clearance
b. Check all wirings
c. Call service
d. Check for setting
a. Check compressor windings, start
relay and overload protector.
b. Check for condenser fan
c. Clean condenser
d. Call service for removing refrigerant
e. Call service for information
running
a. Reset FON
a. Check all wirings and connections
fan
and
air
short