KEYPAD MESSAGES

The GEM-RP1CAe2 Keypad can display the following messages. The GEM-RP2ASe2 and GEM-RP3DGTL will display similar
abbreviated messages that may scroll through two screens.
SYSTEM READY CW1 - All zones operating; system can be
armed. GEM-RP1CAe2 only: C = Chime Mode on; W = Watch
Mode on; 1-8 = Area.
PLEASE WAIT - Panel reporting to central station on arming.
Wait for ringback signal to exit.
EXIT TIME XXX SI1 - Exit delay in progress. XXX = exit time
remaining in 10-second decrements; GEM-RP1CAe2 only: S =
Service Code active; I = arming with Instant protection; 1-8 =
Area.
ENTRY TIME XXX - Entry delay in progress. XXX = entry time
remaining in 10-second decrements.
SYSTEM ARMED SI1 - Panel armed. GEM-RP1CAe2 only: S =
Service Code active; I = arming with Instant protection; 1-8 =
Area.
CHECK STATUS CAW - One or more zones not secured.
Display status for zone description(s). GEM-RP1CAe2 only: C =
Chime Mode on; W = Sensor Watch Mode on
CAN'T ARM/ZONES NOT NORMAL - Arming attempted with
Priority Zone in trouble. Secure zone to arm.
DAY ZONE TRBL - Trouble condition on Day Zone, followed by
one or more zone descriptions.
INVALID ENTRY/TRY AGAIN - Wrong code/time/area number
entered.
CAN'T ARM SYSTEM - Arming attempted with System Trouble
present. Press the
C
button and then arm the system.
ALARM - Alarm condition, followed by one or more zone
descriptions.
****FIRE**** - Fire alarm condition, followed by one or more zone
descriptions.
FIRE TROUBLE - Trouble condition on a Fire Zone. Press
C
button to silence the sounder. Correct the trouble, then
press the
button again.
C
FIRE ALARM - Alarm condition on a Fire Zone. Press the
C
button to silence the sounder. Correct the cause of the
alarm, then press the
C
ZONES BYPASSED - (When Zones Bypassed displayed)
Indicates zones that have been deactivated.
OV(R-) - Overview Mode (Status of up to 8 areas): R=Zone
Ready; also, Z=Zone Fault; A=Armed; B=Burglary Output;
F=Fire Alarm; T=Fire Trouble; C=Check Trouble; Display Mode.
SYSTEM TROUBLE - A System Trouble display will be followed
by one or more of the following error codes:
E01-00 - AC POWER FAIL. Power failure. Check power
transformer. Check for blown fuse or circuit breaker;
general power outage.
E02-00 - LOW BATTERY. Battery below 11 volts. If not
recharged within 24 hours, replace it.
E03-00 - COMM FAIL. Unsuccessful communication to
central station. Note: Will also display if panel improperly
programmed to report; i.e., Report Alarm, Report Codes,
Subscriber ID Numbers, etc. must be programmed.
E04-NN - WL TRBL. Wireless transmitter supervisory
failure. NN = transmitter number.
E05-NN - WL LOBATT. Rf transmitter low battery.
NN = transmitter number.
E06-NN - RF REC TROUBLE. Rf receiver response
X
GEM-P9600 Installation Instructions
button again.
trouble. NN = receiver number.
E07-00 - DOWNLOAD FAIL. Download failure.
E08-00 - TELCO LINE1 FAIL. Telephone line failure
(system trouble displays after a programmed delay).
E09-00 - NOT PROGRAMMED. System cold start.
E10-NN - BURG KEYPAD TRBL. Keypad response failure.
NN = keypad number.
E11-NN - BURG KPD TAMPER. Keypad cover removed.
NN = keypad number.
E12-NN - BURG EZM TRBL. Expansion zone module
failure. NN = module number.
E13-NN - BURG EZM TAMPER. EZM module cover re
moved. NN = module number.
E14-NN - RELAY BOARD TRBL. Relay board response
failure. NN = relay board number.
E15-NN - WL TAMPER. Transmitter cover removed.
NN = transmitter number.
E16-NN - RF REC JAMMED. Receiver jammed.
NN = receiver number.
E17-NN - RF REC TAMPER. Receiver cover removed.
NN = receiver number.
E18-NN - LOBATT KEYFOB. Key fob transmitter low
battery. NN = key fob transmitter number.
E19-00 - USER MEM ERROR. Internal memory error.
Select RESET SYSTEM TBL. Press the
the
button.
C
E20-00 - DEALER MEM ERROR. Same as above.
E22-NN - PIR SENSOR TRBL. No trip detected on PIR
Supervision Zone within programmed Sensor-Watch time.
NN = Zone number. To reset, press YES (
button at "RESET SENSOR MSG" function display.
E23-00 - BURG BUS FAILED. Failure of 4-wire bus. Check
Terminals 11/12.
E24-00 - TIME FOR SERVICE. A service message can be
programmed through the PCD3000 Quickloader
(event-schedule screen) to remind the user to arrange for
scheduled maintenance. At the programmed date and time,
the keypad sounder will start to pulse and the display will
read "TIME FOR SERVICE" (GEM-RP1CAe2) or "SERV"
(GEM-RP2ASe2). This condition will behave as a system
trouble and may be cleared as such, i.e., press
silence sounder; access RESET SYSTEM TRBL, then press
J
the
button.
E39-00 - RF CAPACITY TRBL. Receiver capacity error.
E51-00 - Alarm Output Supervisory.
E99-00 - Keypad panic shorted too long. GEM-RP2ASe2 /
GEM-RP3DGTL only.
NN OUT OF SYSTEM - Keypad inoperative. NN = keypad
number.
ALARM - (After panel is disarmed) displays zones violated.
FAULT FIND - Fault-find Mode activated.
LOCATE - Locate Mode activated.