Figure 21. Knockout Pattern For Remote Battery Disconnect - Powerware 9350 Installation Manual

1085 series; 685 series; auxiliary battery cabinets
Table of Contents

Advertisement

Table A. Remote Battery Disconnect Power Terminations
Terminal
E4 (+)
E5 (---)
Breaker (+)
Breaker (---)
Breaker (jumper)
Battery Cabinet (+)
Battery Cabinet (---)
Battery Cabinet
Series 685
Series 1085
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
E
T
A
A
E
T
E

Figure 21. Knockout Pattern for Remote Battery Disconnect

Size of Pressure Termination
1 --- #8---3/0
1 --- #8---3/0
1 --- #4---300 kcmil
1 --- #4---300 kcmil
1 --- #4---300 kcmil
See Table C (Appendix A)
See Table C (Appendix A)
Table B. Battery Cabinet Terminations
(1) #2---1/0 kcmil [Breaker (+) & (---)]
(1) 3/0---250 kcmil [Breaker (+) & (---)]
E
T
A
T
E
T
A
T
E
Terminal Function
UPS Battery Contactor K2 (+)
UPS Battery Contactor K2 (---)
Battery Disconnect (+)
Battery Disconnect (---)
Battery Disconnect (jumper)
Stand---alone battery cabinet (+)
Stand---alone battery cabinet (---)
Size of Pressure Termination
T
A
A
T
35