Instrument Calibration

The current values reflect the values presently maintained by the system. The user can perform a one-point calibration
by entering an offset value into the respective column. This will automatically adjust the current value and zero out the
offset value. Giving max and min values for a respective current value can perform a two-point calibration. The
program will automatically adjust the calibration line to meet those values.
The following items can be calibrated at this screen: Discharge Pressure Transducer, Suction Pressure Transducer,
Manifold Pressure, 0-10v Input, Oil Filter Inlet Pressure Transducer, Discharge Temperature RTD, Suction Temperature
RTD, Oil Injection Temperature RTD, Oil Separator RTD, Process Temperature RTD and Motor Amperage.