Calibration Procedure Of Optical Actuators - Emerson Vission Control Manual

Microcontroller panel
Table of Contents

Advertisement

Calibration Procedure of Optical Actuators

* If you are replacing or reinstalling a new optical actuator see: page 63 first.
ACTUATOR MOTOR CONTROL MODULE
CALIBRATION PROCEDURE
1. Disable the Slide Non-Movement Alarm by
going to the "Setup" menu on the Vission/
Vantage and choosing "Alarm Disable" for the
Slide Non Movement Option.
2. Open the plastic cover of the capacity motor by
removing the four #10 screws. Caution: there
are wires attached to the connector on the
plastic cover. Handling the cover too aggres-
sively could break the wires.
3. Gently lift the cover and tilt it toward the Turck
connectors. Raise the cover enough to be able
to press the blue calibrate button and be able to
see the red LED on the top of assembly.
4. Press "Menu" on the main screen and then press
the "Slide Calibration" button, to enter the slide
calibration screen. If you are re-installing a new
optical actuator re-connect the yellow and gray
cables.
5. Press INC and DEC to move the slide valve and
check for the correct rotation. See Table 1 for
Actuator/command shaft rotation specifications.
6. Note: If the increase and decrease buttons do
not correspond to increase or decrease shaft
rotation, swap the blue and brown wires of the
"yellow power cable". This will reverse the
rotation of the actuator/command shaft.
51

Advertisement