System Control Limit Values Work Sheet - Emerson Vission Control Manual

Microcontroller panel
Table of Contents

Advertisement

SYSTEM CONTROL LIMIT VALUES WORKSHEET
CONTROL
LIMITS
SUCTION PRESSURE ON/OFF (1)
SETPOINT #1
SETPOINT #2
SUCT PR CAP INCREASE
SETPOINT #1
SETPOINT #2
SUCT PR CAP DECREASE
SETPOINT #1
SETPOINT #2
HIGH DSCH PRESS UNLD
SETPOINT #1
SETPOINT #2
LIQ INJECTION SOLENOID CONTROL
TEMP VIA:
OIL INJECTION TEMPERATURE
OIL SEPARATOR TEMPERATURE
OILPMP RESTART (D/S)
OIL SEPARATOR HEATER
CAP CTRL °F ON/OFF
SETPOINT #1
SETPOINT #2
CAP CTRL °F INCR
SETPOINT #1
SETPOINT #2
CAP CTRL °F DECR
SETPOINT #1
SETPOINT #2
LAG, CAPACITY STEP
VOL SLIDE ADJ FACTOR
MINIMUM RUN CAPACITY
LEAD, MAXIMUM CAP FLAG
ECONOMIZER SOLENOID
VOL ADJ CAP RANGE
LOW SUCTION PRESS LOAD LIMIT
SETPOINT #1
SETPOINT #2
LOW SUCTION PRESSURE LOAD LIMIT
SETPOINT #1
SETPOINT #2
MOTOR AMPS LOAD LIMIT
SETPOINT #1
SETPOINT #2
CURRENT TRANSFORMER
NOTES:
(1)
Must be field set.
(2)
Set only if temperature is used for capacity control.
(3)
Set only if Lead/Lag option is selected.
(4)
Set FLA at nameplate amps, MAX at nameplate + service factor.

System Control Limit Values Work Sheet

SYSTEM VALUES
CUT IN
CUT OUT
(1)
(1)
(1)
(2)
(2)
(2)
(3)
(3)
(4)
C/T RATIO
(1)
VALUE LIMITS
CUT IN
CUTOUT
30"/150
30"/150
30"/150
30"/150
30"/150
30"/150
30"/150
30"/150
30"/150
30"/150
30"/150
30"/150
0/300
0/300
0/300
0/300
ON
OFF
200°F
50°F
200°F
50°F
1.0/8.0
1.0/8.0
80/130
80/130
-99/200
-99/200
-99/200
-99/200
-99/300
-99/300
-99/300
-99/300
-99/200
-99/200
-99/200
-99/200
0/100
- - -
-100/100
- - -
10% / 90%
- - -
50/100
50/100
0% / 100%
0% / 100%
0/100
- - -
ON
OFF
0/999
0/999
0/999
0/999
C/T RATIO
100-1000/AMPS
DEFAULT VALUES
CUT IN
CUT OUT
10
6
15
11
20
25
20
25
18
23
18
23
200
190
210
200
ON
OFF
120°F
105°F
120°F
105°F
2.8
3.0
95
105
20
10
25
15
28
27
33
32
24
25
29
30
10
- - -
0%
- - -
30
- - -
95
90
80%
75%'
100%
100%
ON
OFF
30
35
40
45
5
10
5
10
C/T RATIO
100/5 AMPS
81