See section on saving changes. After back- ing up the setpoints DO NOT power down the Vission panel for at least 1 minute. This will allow adequate time for all setpoints to be properly saved.
Installation Instructions For Replacement Of Optical Actuator......54 Slide Valve Actuator Troubleshooting Guide ............55 Slide Wiring Diagram for Models Vission VSM-91 To VSS-601 ......59 Slide Wiring Diagram for Models Vission VSS-751 To VSS-1801 ..... 60 Command Shaft Rotation and Travel ..............61 Calibration For Earlier Style Mechanical Gearmotor/Potentiometers .....
Page 6
System Setpoints Alarms and Trips Work Sheet ..........80 System Control Limit Values Work Sheet .............. 81 System Timer Values....................82 Spare Parts ........................ 84 Modifications for Analog Board (Vission/Vantage after July 2003) ....85 Danfoss Liquid Injection Valves ................87 Who to Contact ......................88...
STANDARD VILTER WARRANTY STATEMENT Seller warrants the products it manufactures to be free from defects in material and workmanship for a period of eighteen (18) months from the date of shipment from Seller s manufacturing plant or twelve (12) months from date of installation at the initial end users location, whichever occurs first.
Wiring Instructions For Vission Only Mandatory Wiring Step #2 1-2 Safety Motor Starter Contactor Connection 1-6 " The contact to the pull in the motor starter contactor is a dry contact, place a "HOT" wire from the starter circuit on 7-1.
Page 14
Wiring Instructions For Vission Only Mandatory Wiring Step #3 1-2 Safety Motor Starter Auxilary Contact 1-6 " "HOT" to 4-5 Wire to energize to 1-1 1-10 2-10 3-1 "N" 3-5 "N" 3-10 4-10 5-10 6-10 View Inside Of Vission Panel...
Page 15
Wiring Instructions For Vission Only Mandatory Wiring Step #4 1-2 Safety Oil Pump Starter Connection 1-6 " "HOT" to 6-1 Wire to energize on 6-2 1-10 2-10 3-1 "N" 3-5 "N" 3-10 4-10 5-10 6-10 View Inside Of Vission Panel...
Page 16
Wiring Instructions For Vission Only Optional Wiring Step #5 Auxiliary / Safety Wiring 1-2 Safety A determination by the user is to be made if this option will be used. If it is not used, insure that a jumper is installed 1-6 "...
Page 17
Wiring Instructions For Vission Only Optional Wiring Step #6 Remote Start Wiring 1-2 Safety A determination by the user is to be made if this option will 1-6 " be used. If it is not used, insure that a jumper is installed between L 2-1 and 1-5.
Page 18
Wiring Instructions For Vission Only Optional Wiring Step #7 Setpoint #1/#2 Selection Wiring 1-2 Safety A determination by the user is to be made if this option will 1-6 " be used. This optional input does not need to be closed for the compressor to run no jumper is required.
Main Screen The Main Screen This screen has been designed to give This Screen contains buttons to navigate the operator an overall view of all operating to setpoint, setup and maintenance screens. parameters affecting the compressor pack- age. This screen should always be displayed Status information on the compressor, oil pump, when maintenance items and setpoint items oil heater and run mode.
Set Up Screen From the Main screen, touch the Setup but- ton. After entering an authorized user name password, the screen pictured below will ap- pear. ·Operator Name – This is the same list that appears in the login dialog. Names in this list can be selected for deletion.
Page 24
This determines which measured vari- node addresses are not allowed. The node able is used in making loading (capacity con- address of each Vission is determined through trol) decisions. The choice selected here de- the SETUP menu. The MicroController that...
This screen is also used to backup and save setpoints by pressing (Backup Settings). After performing a “Back up Setting” operation, DO NOT power down the Vission/Vantage panel for atleast 1 minute. This will allow adequate time to insure all setpoints have been properly stored.
Maintenance Screen Touch Here From the Main screen touch the Maintenance button. “Service Item Required” message indicates that the compressor runtime hours has accumulated to a value - or a point- where service Maintenance is required. >From the main screen, press the “Maintenance” button. A chart will be shown to indicate what service is required - based on the number of hours the compressor has run.
Page 27
Maintenance Screen This screen shows the chart of routine maintenance to be performed on the machine at hourly intervals from 200 hours to 120,000 hours. The Service Button from the Maintenance Screen will bring you to this screen. When entering service items that were completed, make sure to check all items that are listed to be done at that service interval.
Menu Screen At the bottom of the Main screen touch the Menu button to bring up the screen shown in Figure below. Use this screen to navigate to the other setpoint screens contained within the program. Each screen has a help button to describe the func- tion of the screen.
Common Buttons Common Buttons There are several buttons that are common for all menu screens: · Return to Menu – This button always returns you to the Menu screen · Logon To Edit – The user is allowed to view data at all screen levels but cannot edit data until a login has occurred.
Compressor Control Level 1 Access – Compressor Control Setpoints From the Menu screen , press the Compressor Control setpoints button. The compressor control setpoints screen will be shown. fault settings of 3 and 20 seconds respectively, pro- hese screens enable the operator to view and vide good operation over a wide range of condi- adjust settings that affect compressor control.
Page 31
Compressor Control Setpoints on this screen: · Suction Pressure On/Off – The compressor perature safety trip value. This will shut down will automatically cycle ON and OFF at the the unit and a reset will be required to restart setpoints entered. Suction Pressure On/Off control is only active if the Compressor Con- trol Via Suction Pressure option is selected ·...
Additional Compressor Controls · High Discharge Pressure Unloading limit will only prevent the compressor from Setpoints 1&2 – Active in Suction Pressure or loading and does not shut down the compres- Process Temperature Capacity Control mode. sor if the maximum current draw setpoint is These setpoints limit the compressor from exceeded.
Page 33
Compressor Control Capacity setpoint. On a call for unloading, the · Oil Separator Heater Temperature – This con- compressor will unload until it reaches the Mini- trol limit determines when the oil separator mum Run Capacity control setpoint. It will re- heater is energized.
Page 34
· Low Suction Pressure Load Limit – Active in Dis- charge Pressure Capacity Control mode only. These setpoints limit the compressor from loading at low suction pressure conditions. They override the dis- charge pressure capacity control setpoints. When the OFF setpoint is reached (at or below setpoint), the compressor will not be allowed to load any fur- ther.
Compressor Alarm and Trip · Low Suction Pressure Setpoints 1&2 – This · High Discharge Temperature – This is the is the low suction pressure safety. This safety high discharge temperature safety. The alarm is active in both temperature and pressure or trip will be active if the discharge tempera- control modes.
Compressor Alarm and Trip setpoint. The alarm or trip will be active if the oil temperature of the separator drops be- low the setpoint value. · Low Oil Injection Temperature – This is the low oil injection safety. The alarm or trip will be active if oil injection temperature drops below setpoint value after a time delay (Oil Injection Temperature Safety Changeover).
Compressor Setpoints and Alarms · High Filter Differential Pressure Start – This · Prelube Oil Pressure – If the oil pressure does safety setpoint is active when the compressor is not rise above the reset setting for a time exceed- in the start cycle.
Page 38
Compressor Timer Setpoints To change a timer setting, you must “Logon to Edit” first. Push the “Set” button then push on the timer setpoint value you wish to change. After the setpoint is changed, press the “Refresh” button. This will refresh the “Current”...
Page 39
Compressor Timer Setpoints · Minimum Compressor Prelube Timer – This is the · Oil Separator Temperature Safety Changeover length of time the oil pump will run after establish- – This timer allows Low Oil Separator Start ing the Prelube Oil Pressure, to prime oil circuit Temperature Safety setpoint to protect the com- before starting the compressor.
Page 40
Compressor Timer Setpoints The compressor restart options (Hot Starts or Anti-Recycle Timers) are selected from the Setup screen. One additional Anti-Recycle Timer that can be selected from the Setup screen is the Modified Anti-Recycle Timer. · Modified Anti-Recycle Timer – Normally, this anti-recycle timer will function as a True Anti- Recycle Timer.
Miscellaneous Screens (Condenser Control) This screen is designed for customized functions only, thus maybe placed as a view only screen. Note: Changing variables on this screen will not have any effect unless you have a customized program for your unit. To View if a customized program has been installed in your unit, go to the main screen and press VERSION, a screen will appear with the program version and the make model of the unit.
Page 42
Miscellaneous Screens (Motor Speed) This screen is designed for customized functions only, thus maybe placed as a view only screen. Note: Changing variables on this screen will not have any effect unless you have a customized program for your unit. To View if a customized program has been installed in your unit, go to the main screen and press VERSION, a screen will appear with the program version and the make model of the unit.
Compressor Sequencing (Max 5 Compressors) You must clear the IP From the Main Menu (press sequencing), this screen will appear. Address before entering a new one.
Page 44
Compressor Sequencing (Max 5 Compressors) Note: Sequencing and Remote/Start-Stop can NOT fuction at the same time- Sequencing will over-ride remote start/stop! This screen allows the operator to setup a sequenc- Equipment: Ethernet IP Address ing network. Currently, the MicroController is ca- Cmp#1: 10.8.0.73 pable of sequencing 5 compressors.
Page 45
Compressor Sequencing (Max 5 Compressors) · Node – These node address fields tell the se- · Min Cap – The Minimum Capacity is the lowest quencing algorithm which the MicroController capacity, in percentages, that this compressor is will be participating in the sequencing net- allowed to reach during operation.
Page 46
Compressor Sequencing (Max 5 Compressors) · Unload Rate 1 – If the system pressure falls be- low the Unload Rate 1 pressure setpoint for the time specified in the Unload Rate 1 Timer, Central Control will attempt to decrease the capacity of the system.
Vilter Only Screen WARNING: Settings on these screens should be used only by Vilter represen- tatives or persons acting under their direction. Improper setting may result in loss of vital data and require service NOT covered under warranty.
Diagnostics Force Output · On/Off – This will turn the force outputs option On/Off. The force outputs that can be modified are as follows: Main Motor Starter, Oil Pump, Economizer Solenoid, Remote Alarm/Trip, Liquid Injection Solenoid, Capacity Increase Motor, Capacity Decrease Motor, Volume Increase Motor and Volume Decrease Motor. You can choose the forced output by pressing the down arrow in the control labeled Available Outputs.
Instrument Calibration The current values reflect the values presently maintained by the system. The user can perform a one-point calibration by entering an offset value into the respective column. This will automatically adjust the current value and zero out the offset value.
Instrument Calibration nstrument calibration menu displays the Input channels that can be calibrated to represent the actual values at the sampling points. The current values reflect the values presently maintained by the system. The user can perform a one point calibration by entering an offset value into the respective column.
“Slide Calibration” button, to enter the slide 1. Disable the Slide Non-Movement Alarm by calibration screen. If you are re-installing a new going to the “Setup” menu on the Vission/ optical actuator re-connect the yellow and gray Vantage and choosing “Alarm Disable” for the cables.
5V position) has been set. to the maximum position. 12. Use the INC button on the Vission/ Note: The “Slide calibration” screen on Vantage panel to drive the slide to its the Vission/Vantage has a “Current”...
Page 53
2783J qualified analog boards applies to Repeat the same procedure to the other only VISSION). You are nearing the mechani- channel. cal stop position. 17. Pulse the INC button to carefully move the slide valve until the millivolt readout “satu-...
0-5 Volts, the controll ing channel corresponding to the actuator motor ( either the capacity or volume) has to be calibrated. This instructs the Vission/ Vantage control panel to learn the rotational 0% position & rotation 100% position of the slide valve travel.
Slide Valve Actuator Troubleshooting Guide Slide Valve Actuator Theory of Operation manually while the power is off or the motor brake has failed, allowing the motor to free wheel for too long The slide valve actuator is a gear-motor with a posi- after the position sensor looses power, the actuator will tion sensor.
Page 56
Slide Valve Actuator Troubleshooting Guide The actuator cannot be cali- Dirt or debris is blocking one or both Clean the optocoupler slots with optocoupler slots a Q-Tip and rubbing alcohol. brated The photochopper fence extends less Adjust the photochopper so that than about half way into the the fence extends further into the optocoupler slots...
Page 57
Slide Valve Actuator Troubleshooting Guide The actuator does not transmit The motor was manually moved Recalibrate. the correct position after a while the position sensor was not power loss powered. The motor brake is not working Get the motor brake to where it op- properly erates freely and then recalibrate.
Page 58
Slide Valve Actuator Troubleshooting Guide Replace the actuator. The motor runs sporadically Bad thermal switch See above. Any of the reasons listed in “The mo- tor will not move in either direction” The motor runs but output shaft Replace the actuator. Stripped gears inside the gear motor will not turn or the armature has come un-pressed...
Calibration For Earlier Style Mechanical Gearmotor/Potentiometers will show a value, but it has no meaning at · Capacity Slide Valve Potentiometer Calibra- this point. Now turn the command shaft to tion – Move the capacity slides to their mini- the fully loaded position. With the slide mum position.
Page 63
Calibration For Earlier Style Mechanical Gearmotor/Potentiometers and 1100 millivolts. Without changing the gear mesh, remove one ¼” screw, and apply Loctite #242 to the threads. Reinstall the screw finger tight, then repeat the procedure on the remain- ing screw (do not change the orientation of the lockwashers on the screws).
Trend Chart The trend analysis screen shows recorded data for a logging range of either 60 minutes or 120 hours. Additionally, selections can be made to display segments of the logged data. To view which selections are being shown hit the data select button. Note: When the panel is powered down, and powered back up, the “Trend Screen”...
Data Select Screen The user has the ability to select which value they would like to see displayed on the graph. Only four selections can be chosen at once to view, even though all data is being accumulated.
Event List Touch Here From the Menu screen, touch the Event List button. The screen on the next page will appear.
Page 67
Event List The Event List will give a chronological record of the last 40 events recorded by the controller. These events can be filtered by selecting the Filter box on the upper left of the screen.
Trouble Shooting Flowchart (Vission Only) Check to make sure 120VAC is run to “L1” on the Relay board. This is the board on the inside left back of the panel. “L1” is the fifth connector down from the top and the top terminal.
Page 69
Trouble Shooting Flowchart (Vission Only) There are four fuses on the Analog board that limit the current on the 24VDC to the Analog channels. The fuses are 500 milliamp, located near the power supply connec- tors and brown in color. LEDs next to the fuses give a visual indication of the status of the fuse, however, it is best to pull the fuse and check them with an ohmmeter.
Safety Failure Message Suction Pressure SP#1 Fail - This message will appear when the suction pressure falls below the safety setting of the Lo Suction Pressure Trip Setpoint No.1. In addition, this message will appear when the suction pressure reading rises above 300 PSI, indicating an open transducer or bad analog channel.
Page 71
Safety Failure Message Percent Volume Fail – This message will appear if the percent volume reading exceeds 300% or goes below –15%. Lo Control Temperature Fail – This message will appear when the Process Control Temperature falls below the safety setting of the Lo Control Temperature Trip Setpoint. In addition, this message will appear when the Process Control Temperature rises above 300 degrees F, indicating an open RTD.
Page 72
Safety Failure Message Run Filter Diff Press Fail – This message will appear if the Filter Differential pressure rises above the High Fltr Diff Press – Run setpoint after the Filter Differential Pressure Safety Changeover timer times out. Maximum Amperage Fail – This message will appear if the motor amperage rises above the Hi Motor Amps trip setpoint.
Copy Down All Setpoints As These Will Need To Be Re-entered When New Flashcard Is Installed. Hit The Emergency Stop Botton Located In Front Of the Panel Verify Unit is Shut Down Completely VANTAGE/VISSION Verify Lockout Disconnect On Compressor Start. EMERGENCY This Ensures Compressor Does Not Start. STOP BUTTON...
Flash Card Installation Instructions Press Latch To Release Flashcard Remove Flashcard And Replace Flip Board Back Into Postion Secure Board To Mounts With Previously Removed Screws Reconnect Connectors and Ribbons Note: You Must Re-enterSetpoints And Recalibrate SlideValves. See Section On Setpoint Values And the Section On Optical Actuators.
Back Light Installation Instructions Remove (Four) Nuts Remove Board Flip Board Over Unplug Connector Disconnect Ribbon Remove (Four) Screws And Turn Board Over...
Page 77
Back Light Installation Instructions Remove Small Screw And Slide Back Light Out As Shown Slide New Back Light In And Secure With Previously Removed Screw...
Page 78
Back Light Installation Instructions Place Board Back Into Postion And Secure Connect Ribbon And Plug Connector Back In Place Board Back Onto Back Of Panel And Secure With Previously Removed Nuts...
System Control Limit Values Work Sheet SYSTEM CONTROL LIMIT VALUES WORKSHEET CONTROL SYSTEM VALUES VALUE LIMITS DEFAULT VALUES LIMITS CUT IN CUT OUT CUT IN CUTOUT CUT IN CUT OUT SUCTION PRESSURE ON/OFF (1) SETPOINT #1 30”/150 30”/150 SETPOINT #2 30”/150 30”/150 SUCT PR CAP INCREASE...
System Timer Values The values or options in the screen displays shown must be entered before start-up. SYSTEM CONTROL LIMIT VALUES WORKSHEET TIMER VALUES SYSTEM VALUES VALUE LIMITS DEFAULT VALUES AT START CAPACITY DECREASE 0/999 SEC 15 SEC CAPACITY INCREASE MOTOR ON 0/255 SEC 2 SEC CAPACITY DECREASE MOTOR ON...
Spare Parts PART DESCRIPTION VILTER PART NUMBER QTY. Analog Board (VISSION PANEL) 3011A Analog & Relay Board (VANTAGE PANEL) 3011C1 Control Relay, 4PDT 3011B1 Control Relay, DPDT 3011A1 Control Relay, SPDT 3011Z Input Module 2895M (120v) Output Module 2895N (120v)
Modifications for Analog Board (Vission/Vantage after July 2003) Using Danfoss Transducers with 2783J qualified boards The analog boards used in the Vission and Vantage panels after July 2003 have been modified to ac- commodate the use of Danfoss transducers (VPN 2783J).
Page 86
Modifications for Analog Board (Vission/Vantage after July 2003) The procedure to Change Scale Factors on 2783J Qualified Board 1. From the Main Screen, press the Menu button. 9. Press the Clear button. Now press the buttons 2. From the Menu Screen, press the Vilter ONLY 4297, followed by pressing the “Enter”...
Danfoss Liquid Injection Valves Press “Setup” Select “Enable” for Liquid Pos. Valve Press “OK” Press “Vilter Only”, you will be prompted to Log In Press “Liquid Inj. Temp Control” then you will see the screen as in the attached picture “Liquid Inj. Control”, the values you see there are default and can be changed according to your application.
PO Box 8904 Cudahy, WI 53110-8904 Tel: 414-744-0111 Fax: 414-744-1769 e-mail: info.vilter@emerson.com www.vilter.com Note: It will be necessary to have your Vilter order number available when contacting Vilter Manufacturing Corporation for service support. Disclaimer: Specifications are subject to change without notification.