System Control Limit Values Work Sheet; System Timer Values - Emerson Vission Control Manual

Microcontroller panel
Table of Contents

Advertisement

The values or options in the screen displays shown must be entered before start-up.
SYSTEM CONTROL LIMIT VALUES WORKSHEET
TIMER VALUES
AT START CAPACITY DECREASE
CAPACITY INCREASE MOTOR ON
CAPACITY DECREASE MOTOR ON
CMP STARTER AUX CONTACT BYPASS
CAP INCREASE MOTOR OFF
CAP DECREASE MOTOR OFF
VOL SLIDE ADJ TIMER
MINIMUM CAP PRELUB TIME
RUN CYCLE OIL PRESS BYPASS
PRELUB PUMP TIME LIMIT
FLTR DIFF PR SAFETY CHANGEOVER
LO OIL SEP LEVEL BYPASS TIMER
AUTO RESTART AFTER POWER FAIL
OIL SEP TEMP SAFETY CHANGEOVER
LO OIL INJ TEMP SFTY CHANGEOVER
ANTIRECYCLE STRT TIMER (MIN)
FORCE START LAG COMP (MIN)
HOT STRTS/HR COUNTER (COUNTS)
NOTES:
(1)
Must be field set.
(2)
Set only if Lead/Lag option is selected.
82

System Timer Values

SYSTEM VALUES
(1)
(2)
(1)
VALUE LIMITS
DEFAULT VALUES
0/999 SEC
15 SEC
0/255 SEC
2 SEC
0/255 SEC
2 SEC
0/255 SEC
10 SEC
0/255 SEC
20 SEC
0/255 SEC
10 SEC
0/255 SEC
20 SEC
0/255 SEC
5 SEC
0/90 SEC
60 SEC
0/255 SEC
255 SEC
0/999 SEC
60 SEC
0/120 SEC
60 SEC
1/240 MIN
5 MIN
0/15 MIN
5 MIN
0/15 MIN
6 MIN
0/30 MIN
20 MIN
0/60 MIN
30 MIN
1/10 COUNTS
3 COUNTS