Description Properties; Alarms - Emerson E2 Einstein User Manual

Flexible combiner programming
Hide thumbs Also See for E2 Einstein:
Table of Contents

Advertisement

1.6

Description Properties

Figure 1-9
- Flexible Combiner Description Properties
The Description Properties screen will show the
descriptions of the associated inputs and outputs entered
by the user. Pertinent descriptions can be entered that
explain inputs and outputs to aid in understanding the
intent of the programming performed in the flexible com-
biner. (Descriptions for analog memory outputs appear
only in expanded status.)
If text is not entered for a description for an input and a
connection is made to the output of another application,
the description is automatically filled in with the applica-
ton name and property of that output. If text is entered for
an input and a new connection is made, the text is not
automatically changed. This applies to inputs only; out-
puts are not affected.
Description Properties
1.7

Alarms

Figure 1-10
- Flexible Combiner Alarm Setup
The alarm output and delay equations control the trig-
ger of the alarm and how long to delay before setting an
advisory in the advisory log. These equations are executed
exactly like analog and digital outputs. The alarm output
equations combined with the delay equations control the
outputs AL1 - AL4. The results of the delay equation are
sent to outputs AL1 - AL4 DELAY. The alarm type can be
set to either Notice or Alarm. The alarm priority sets the
priority of the advisory generated. For a complete list of
advisory text, see the Appendix section.
-