Condition
Shipping and storage (in factory packing)
Acoustic specifications
The acoustic emission specifications for the disk array are:
•
8.27 Bels (A) sound power
•
65 dB (A) sound pressure, operator position (1 meter from the floor and surface of the rack)
You can reduce the ambient noise level caused by equipment and air conditioning blowers in your
computer room by:
•
Installing a dropped ceiling covered in commercial-grade, fire-resistant, acoustic-rated, fiberglass
ceiling tile
•
Covering the walls in sound-deadening material
•
Installing foam rubber removable partitions
Heat dissipation, power consumption, and air flow
Table 15
describes the heat dissipation and power consumption of the HP XP12000 disk array when
loaded with the maximum number of disk drives.
Table 15 Maximum heat dissipation and power consumption specifications
Parameter
Power consumption (kVA)
Heat dissipation (kW)
BTUs per hour
kcal per hour
Table 16
shows frame air flow requirements.
Table 16 Air flow specifications
Product No.
AE002A
AE045A
Table 17
presents the heat dissipation and power requirements of individual components.
Table 17 Component heat dissipation and power consumption specifications
Product No.
AE002A
26577
Description
HP XP12000 Disk Control Frame (DKC)
HP XP12000 Disk Array Frame (DKU)
Description
HP XP12000 Disk Control Frame (DKC)
Specification
Horizontal, incline impact: 1.22 m/sVertical, rotational
edge: 0.1 m
DKC
Each DKU
7.9
7.5
7.8
6.9
23698
6697
5972
Air flow(cubic meters/minute)
XP12000 Disk Array Site Preparation Guide
Full array (1 DKC and 4
DKUs)
37.8
35.5
121369
30584
44
31
Heat
Power
Output(kW)
Consumption(kVA)
1.178
1.219
39
Need help?
Do you have a question about the StorageWorks XP12000 - Disk Array and is the answer not in the manual?