3 Electrical specifications
The detailed electrical specifications in this chapter are provided to help your site electrician perform
any necessary electrical work related to site preparation.
AC line voltage requirements
Power specifications are presented in the following tables. Please note that in all tables 208 VAC is
60 Hz only. Units with only two power cords require only two circuit breakers.
Table 23 50-amp, 50 or 60 Hz, single-phase DKC power specifications
Parameter
Minimum operating voltage (VAC)
Maximum operating voltage (VAC)
Rated line current per power cord
(amps RMS)
Number of power cords
Recommended circuit breakers (amps)
Number of circuit breakers
Dropout carry-through time at
minimum line voltage (ms)
Table 24 30-amp, 50 or 60 Hz, single-phase DKC power specifications
Parameter
Minimum operating voltage (VAC)
Maximum operating voltage (VAC)
Rated line current per power cord
(amps RMS)
Number of power cords
Recommended circuit breakers (amps)
Number of circuit breakers
200 VAC
208 VAC
184
191
212
220
22.6
21.7
2
2
50
50
2
2
60
60
200 VAC
208 VAC
184
191
212
220
11.3
10.9
4
4
30
30
4
4
XP12000 Disk Array Site Preparation Guide
220 VAC
230 VAC
202
212
233
244
20.5
19.6
2
2
50
50
2
2
60
60
220 VAC
230 VAC
202
212
233
244
10.3
9.8
4
4
30
30
4
4
240 VAC
221
254
18.8
2
50
2
60
240 VAC
221
254
9.4
4
30
4
49