Floor clearances, DKC and four DKUs

Figure 8 Floor clearances, DKC and four DKUs
Table 10 Overall floor clearance by floor load rating for a DKC and four DKUs
Floor load
rating (kg/m2)
500
450
400
350
300

Environmental requirements

The environmental specifications for operating this system must be satisfied before installation.
36
Site requirements for the HP XP12000 Disk Array
If C=20 cm (7.9
If C=0A+B=
in)A+B=
200
290
410
570
830
If C=40 cm
If C=60 cm
(15.8 in)A+B=
(23.6 in)A+B=
150
100
230
170
330
270
480
400
710
610
If C=100 cm
(39.4 in)A+B=
70
0
130
60
210
130
340
240
530
400

Advertisement