Temperature Specifications; Humidity Specifications - HP StorageWorks XP12000 - Disk Array Site Preparation Manual

Disk array
Hide thumbs Also See for StorageWorks XP12000 - Disk Array:
Table of Contents

Advertisement

*
Check items
Is the computer room free of any
equipment servicing hazards (for
*
example, electrical or data cables that
obstruct access)?
Is the existing floor plan documented?
Has a new floor plan been developed
to include the new array?
Does the new floor plan include
*
adequate space for airflow and
servicing needs?
Does the new floor plan include the
*
clearance required for the floor's load
rating?
Is the computer room structurally
*
complete (walls, floor, air conditioning
system, and so on)?
Is the floor adequate for the equipment
*
load?
Is antistatic flooring or mats installed?
Are there cutouts or channels for cable
routing?
Is there a dedicated analog telephone
line for the optional modem-based
remote support solution (if chosen)?
Is the infrastructure available for the
optional Internet-based remote support
solution (if chosen)?
Is a telephone line available for HP
representative use?
Is a private LAN available?
Can the temperature be maintained
*
between 16 and 32 degrees C?
Can temperature changes be held to
*
less than 10 degrees C per hour?
Can the humidity level be maintained
*
between 20% and 80%?
Is the computer room protected against
*
dust, pollution, and metallic particulate
contamination?
Yes
No
Reference
Preventing equipment servicing
hazards, page 26
The space planning
The space planning
The space planning
Floor clearance
30
General computer room
requirements, page 25
Floor
requirements, page 26
Floor covering
requirements, page 29
Raised floor cutout
specifications, page 27
Data communication
requirements, page 42
Data communication
requirements, page 42
Data communication
requirements, page 42
Data communication
requirements, page 42
Temperature
specifications, page 37
Temperature
specifications, page 37
Humidity
specifications, page 37
Controlling dust and
41
XP12000 Disk Array Site Preparation Guide
process, page 29
process, page 29
process, page 29
requirements, page
pollution, page
15

Advertisement

Table of Contents
loading

Table of Contents