Temperature Specifications; Humidity Specifications; Mechanical Vibration Specifications - HP StorageWorks XP10000 - Disk Array Manual

Hp storageworks xp10000 disk array site preparation guide (ae102-96014, march 2008)
Hide thumbs Also See for StorageWorks XP10000 - Disk Array:
Table of Contents

Advertisement

*
Check items
Has a new floor plan been developed
to include the new array?
Does the new floor plan include
*
adequate space for airflow and
servicing needs?
Does the new floor plan include the
*
clearance required for the floor's load
rating?
Is the computer room structurally
*
complete (walls, floor, air conditioning
system, and so on)?
Is the floor strength adequate for the
*
equipment load?
Is antistatic flooring or mats installed?
Are there cutouts or channels for cable
routing?
Is there a dedicated analog telephone
line for the modem-based remote
support option (if chosen)?
Is the infrastructure available for the
Internet-based remote support option (if
chosen)?
Is a telephone line available for HP
representative use?
Is a private LAN available?
Can the temperature be maintained
*
between 16 and 32 degrees C?
Can temperature changes be held to
*
less than 10 degrees C per hour?
Can the humidity level be maintained
*
between 20% and 80%?
Is the computer room protected against
*
dust, pollution, and metallic particulate
contamination?
Does the computer room support other
*
environmental considerations (such as
vibration and acoustics)?
Yes
No
Reference
The space planning
Floor clearance and cutout
requirements, page 26
Floor clearance and cutout
requirements, page 26
General computer room
requirements, page 23
Air conditioning
31
Floor
requirements, page 25
Preventing electrostatic
discharge, page 23
Floor clearance and cutout
requirements, page 26
Data communication
requirements, page 36
Data communication
requirements, page 36
Data communication
requirements, page 36
Data communication
requirements, page 36
Temperature
specifications, page 31
Temperature
specifications, page 31
Humidity
specifications, page 32
Controlling dust and
35
Preventing metallic particulate
contamination, page 36
Mechanical vibration
specifications, page 32
Acoustic
specifications, page 35
XP10000 Disk Array Site Preparation Guide
process, page 25
requirements, page
pollution, page
13