List Of Accessible Parameters - CLIMAVENETA WWR MTD - MTD/s, BWR MTD - MTD/s Installation And User Manual

Reverse-cycle water/water or ground source heat pumps installation, user, maintenance manual
Table of Contents

Advertisement

LIST OF ACCESSIBLE PARAMETERS

Directory label
Parameters
Ai
AiL1,AiL2,AiL3,AiL4,AiL5,Air1,Air2
CL
Hour, Date, Year
SP
COOL, HEAT, AS
Sr
COOL, HEAT, AS
Hr
CP01, PU01
Directory label
Parameters
CL34, CL42, CL43, CR30, CR31,
Par
AS00, Te00...tE92, AL55, HE12 (BWR only)
Fnc
Eur
EU
PASS
DISPLAYING ALARMS
FAULT
Values display indication
Er01
Values display indication
Er05
Values display indication
Er20
Values display indication
Er 25
Values display indication
Er30
Values display indication
Er31
48
WWR MTD - BWR MTD GB 03/2010
Press the SET key to view the label
Press the SET+ESC key to view the label
CAUSE
pressure switch tripped, manual reset after
3 activations in one hour, incorrect
connection of power supply phases (three-
phase models only)
Low pressure switch tripped, manual reset
after 4 activations in one hour
Differential pressure switch or system
flow switch activated
Manual reset if active for more than 30
seconds
Differential pressure switch or well water
flow switch activated
Manual reset if active for more than 30
seconds
System frost prevention alarm
(manual reset)
Well / source frost prevention alarm
(manual reset)
Parameters for:
Inputs/Outputs
Clock
Setpoint Cooling, Heating, Domestic hot water
Real setpoint
Tens of hours of operation compressors/pumps
Parameters for:
Configuration plant
Reset histrory alarm
Record alarm
Password
Check fault (see high discharge pressure)
Reset manually
Change the position of two phases.
Check the fault
Check inadequate water flow
Check for air in water circuit
Check electrical connection (see unit wiring dia-
gram)
Check inadequate water flow
Check for air in water circuit
Check electrical connection (see unit wiring dia-
gram)
Check water outlet temperature
Check water flow
Check temperature Set Point
Check correct positioning of sensor BT2
Check water outlet temperature
Check water flow
Check temperature Set Point
Check correct positioning of sensor BT3
I A
SOLUTION