TIME BANDS

The HSW12 controller can manage the unit based o the time and the day of the week.
The controller features four time bands in three profiles that can be combined, when programming, with the days of the week.
The profile defines the behaviour of the unit over a 24 hour period.
Time band management must be enabled by parameter tE00 = 1 (tE00 = 0 standard setting).
Programming example
1) Define the profile for each time band, as shown in the following table.
Description
Description
Hour / Minutes
Operating mode ON/Standby
TIME BAND 1
Cool set point
Heat set point
DHW set point
Hour / Minutes
Operating mode ON/Standby
TIME BAND 2
Cool set point
Heat set point
DHW set point
Hour / Minutes
Operating mode ON/Standby
TIME BAND 3
Cool set point
Heat set point
DHW set point
Hour / Minutes
Operating mode ON/Standby
TIME BAND 4
Cool set point
Heat set point
DHW set point
2) Associate one of the three programmed profiles with each day of the week.
The days of the week are identified by the parameters tE01 to tE07; tE01 = Monday, tE02= Tues-
day......tE07=Sunday. Once having displayed the day of the week, tE01 to tE07, select the value 1, 2 or 3 corre-
sponding to Profile 1, Profile 2 and Profile 3 respectively.
Follow the operations shown below to program the profiles and combine them with the day of the week:
30
WWR MTD - BWR MTD GB 03/2010
Profile 1
hours 00 (tE10=0) / min.00 (tE11=0)
ON (tE12=0)
tE13=15
tE14=30
tE15=50
hours 6 (tE17=6) / min.00 (tE18=0)
ON (tE19=0)
tE20=12
tE21=33
tE22=45
hours 9 (tE24=9) / min.00 (tE25=0)
ON (tE26=0)
tE27=15
tE28=30
tE29=50
hours 17 (tE31=17) / min.00 (tE32=0) hours 17 (tE59=17) / min.00 (tE60=0) tE87..tE88
ON (tE33=0)
tE34=12
tE35=33
tE36=45
Esempio profilo 1 da utilizzare
nei giorni feriali
To access directory tE from the main display, press
esc and set together. [esc+set].
Pressing these two buttons enters the menu with the
list of directories.
Use the up and down buttons to scroll to the directory
PAr.
Press the set button and use the up and down buttons
to scroll to the directory tE.
Press the set button to display the first parameter,
tE00. Use the up and down buttons to scroll to the
other parameters.
To set the selected parameter, press the set button
and enter the value using the up and down buttons.
Confirm the changes by pressing the set button or
alternatively cancel by pressing esc.
Profile 2
hours 00 (tE38=0) / min.00 (tE39=0)
ON (tE40=0)
tE42=15
tE42=30
tE43=50
hours 7 (tE45=6) / min.00 (tE46=0)
ON (tE47=0)
tE48=12
tE49=33
tE50=45
hours 7 (tE52=12) / min.00 (tE53=0)
ON (tE54=0)
tE55=12
tE56=33
tE57=45
ON (tE61=0)
tE62=12
tE63=33
tE64=45
Esempio profilo 2 da utilizzare
nei giorni festivi
Profile 3
tE66..tE67
tE68
tE69
tE70
tE71
tE73..tE74
tE75
tE76
tE77
tE78
tE80..tE81
tE82
tE83
tE84
tE85
tE89
tE90
tE91
tE92