Display Installer Parameters - CLIMAVENETA WWR MTD - MTD/s, BWR MTD - MTD/s Installation And User Manual

Reverse-cycle water/water or ground source heat pumps installation, user, maintenance manual
Table of Contents

Advertisement

DISPLAYING INSTALLER PARAMETERS
42
WWR MTD - BWR MTD GB 03/2010
From the main display, press the set button.
Example of displaying the analogue inputs.
For the other I/Os the procedure is essentially the same***.
The display will show label Ai.
(Scroll the other labels using the UP and DOWN buttons
until reaching the desired label).
Press the set button to display the label for the first ana-
logue input (in this case AiL1).
Press the set button again to display the value of AiL1.
Note that the °C icon comes on to indicate that the value
displayed is in degrees centigrade.
***In the case of the digital inputs / analogue inputs config-
ured as digital inputs, the value will be:
- 0 = input inactive (for digital inputs this corresponds to the
input being open, for analogue inputs configured as digital
inputs it corresponds to the input being shorted to earth).
- 1 = input active (for digital inputs this corresponds to the
input being shorted to earth, for analogue inputs config-
ured as digital inputs it corresponds to the input being
open)
To change the value of the parameter press the up and
down buttons.
When having selected the value, press the set button. **
To exit the display and return to the previous level, press
esc.
**NOTE: pressing the set button confirms the new value;
pressing the esc button returns to the previous level without
changing the existing value.
To exit the menu, press esc until returning to the main dis-
play.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents