ELECTRICAL CONNECTIONS

The units leave the factory fully wired. Installation is limited
to connection to the mains electrical supply and connection
of the flow switch and chiller thermal overload switch QF1
(refer to the wiring diagrams).
For all electrical work, refer to the electrical wiring diagrams
in this manual.
It is also recommended to check that:
- The characteristics of the mains electricity supply are ade-
quate for the power ratings indicated in the electrical spec-
ifications below, also bearing in mind the possible use of
other equipment at the same time.
Power to the unit must be turned on only after installa-
tion work (plumbing and electrical) has been completed.
Respect instructions for connecting phase, neutral and
earth conductors.
Voltage must be within a tolerance of ±10% of the rated
power supply voltage for the unit (for three phase units,
the unbalance between the phases must not exceed
3%). If these parameters are not respected, contact the
electricity supply company.
WWR MTD Electrical data at maximum conditions allowed (full load)
Model
Power supply
(V-Ph-Hz)
WWR 0011 MTD
230~50
WWR 0021 MTD
230~50
WWR 0025 MTD
230~50
WWR 0031 MTD
230~50
WWR 0041 MTD
230~50
WWR 0011 MTD/s
230~50
WWR 0021 MTD/s
230~50
WWR 0025 MTD/s
230~50
WWR 0031 MTD/s
230~50
WWR 0041 MTD/s
230~50
WWR 0021 MTD
400-3N~50
WWR 0025 MTD
400-3N~50
WWR 0031 MTD
400-3N~50
WWR 0041 MTD
400-3N~50
WWR 0051 MTD
400-3N~50
WWR 0061 MTD
400-3N~50
WWR 0071 MTD
400-3N~50
WWR 0091 MTD
400-3N~50
WWR 0101 MTD
400-3N~50
WWR 0121 MTD
400-3N~50
F.L.I. Maximum power input
F.L.A. Maximum current input
L.R.A. Start-up current
14
WWR MTD - BWR MTD GB 03/2010
Values at the maximum conditions allowed (full load)
Compressors
System pump
F.L.I.
F.L.A. L.R.A.
F.L.I.
(kW)
(A)
(A)
(kW)
3,3
16,0
58
0,2
3,4
16,0
61
0,2
3,8
19,0
82
0,2
4,6
23,0
97
0,4
4,2
27,0
130
0,4
3,3
16,0
26
0,2
3,4
16,0
27
0,2
3,8
19,0
37
0,2
4,6
23,0
44
0,4
4,2
27,0
59
0,4
3,0
5,5
32
0,2
4,2
6,0
35
0,2
4,0
8,0
48
0,4
5,2
10,0
64
0,4
6,4
11,8
64
0,4
8,2
15,0
75
0,4
8,3
16,0
95
0,8
10,7
21,0
111
0,8
11,2
22,0
118
1,1
16,1
31,0
140
1,1
For electrical connections, use double insulation cable
in conformity with legislation in force in the country
where the unit installed..
A thermal overload switch and a lockable mains discon-
nect switch, in compliance with the CEI-EN standards
(contact opening of at least 3mm), with adequate switch-
ing and residual current protection capacity based on the
electrical data table shown below, must be installed as
near as possible to the appliance.
If these devices are not visible from the electrical pan-
el of the unit, they should be lockable.
An efficient earth connection is obligatory.
The manufacturer cannot be held liable for any damage
caused by the failure to correctly earth the unit.
In the case of three phase units, ensure the phases
are connected in the correct sequence.
Do not use water pipes to earth the unit.
Total
F.L.A.
F.L.I.
F.L.A.
FU1
(A)
(kW)
(A)
1,0
3,5
17,0
1A
1,0
3,6
17,0
1A
1,0
4,0
20,0
1A
2,1
5,0
25,1
1A
2,1
4,6
29,1
1A
1,0
3,5
17,0
1A
1,0
3,6
17,0
1A
1,0
4,0
20,0
1A
2,1
5,0
25,1
1A
2,1
4,6
29,1
1A
0,1
3,2
5,6
1A
0,1
4,4
6,1
1A
2,1
4,4
10,1
1A
2,1
5,6
12,1
1A
2,1
6,8
13,9
1A
2,1
8,6
17,1
1A
4,0
9,1
20,0
1A
4,0
11,5
25,0
1A
5,1
12,3
27,1
1A
5,1
17,2
36,1
1A
I A
Fuses (5x20T 250V)
FU2
FU3
FU4
FU5
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A
1A
8A
0,5A
3,15A