RESET ALARM LOG

Below are the instructions on how to reset the alarm log if the alarm signal Er90 is shown.
To access directory FnC from the main display, press esc
and set together. [esc+set].
the first directory displayed is PAr.
Use the UP and DOWN buttons to scroll to the directory
FnC.
Press the set button to access the Functions menu.
The first label displayed is dEF.
Use the UP and DOWN buttons to select directory EUr.
Press the set button for 3 seconds.
The display shows YES, to confirm that the alarm log has
been reset. Press Esc to exit.